Emerson B83 Manuel d'instruction - Page 2

Parcourez en ligne ou téléchargez le pdf Manuel d'instruction pour {nom_de_la_catégorie} Emerson B83. Emerson B83 8 pages.

B Series

Specifications

The specifications section on this page provide the ratings and other specifications for the B Series.
Available Configurations
Type B33: 1/2 NPT / 12.7 mm
straight through trap
Type B43: 3/4 NPT / 19.1 mm
straight through trap
Type B53: 1 NPT / 25.4 mm
straight through trap
Type B63: 1-1/4 NPT / 31.8 mm
straight through trap
Type B73
: 1-1/2 NPT / 38.1 mm
(1)
straight through trap
Type B83
: 2 NPT / 50.8 mm
(1)
straight through trap
Maximum Allowable Pressure
250 psig / 17.2 barg
1. Add (-HC) at the end of type number for high capacity.
2. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.

Principle of Operation

Thermal actuator is filled at its free length with a liquid
having a lower boiling point than water. On start-up,
valve is normally open. When steam enters trap,
thermal actuator fill vaporizes to a pressure higher
than line pressure. This forces valve into seat orifice
to prevent any further flow. As condensate collects,
it takes heat from thermal actuator, lowering internal
pressure. Line pressure will then compress thermal
actuator to open valve and discharge condensate.
Valve opening automatically adjusts to load conditions
from minimum on very light loads to full lift at
maximum load.

Installation

WARNING
Personal injury or system damage may
result if this steam trap is installed,
without appropriate overpressure
protection, where service conditions
could exceed the limits given in the
Specifications section and/or steam
trap nameplate.
2
(2)
Maximum Operating Pressure
250 psig / 17.2 barg
Maximum Differential Pressure
250 psig / 17.2 barg
Maximum Operating Temperature
450°F / 232°C
Materials of Construction
Body and Cover: Cast Iron ASTM A278 Class 30
Actuator: Welded Stainless steel
Cover and Gasket: Graphite
Valve and Seat: Hardened 416 Stainless steel
Options
SLR Orifice
HC - High Capacity Orifice
Additionally, physical damage to the
steam trap may result in personal injury
or property damage due to escaping of
accumulated gas. To avoid such injury
and damage, install the steam trap in a
safe location.
All pressure equipment should be
installed in a non-seismic area;
should not be exposed to fire; and
should be protected from thunderbolt
(lightning) strikes.
1. Before installing trap, blow steam through
equipment and piping to remove scale, pipe
threading chips and other dirt.
Emerson Thermostatic Bellows Traps do
not require change of body or cover for
different pressures.
2. Check arrows on trap body or cover to ensure
that flow direction is correct. See Figure 2 for
recommended installation.
(2)
(1)
(2)
Note