FB2100/FB2200 Flow Computer I/O Termination Board Field Replacement Guide
Replacing the I/O Termination Board
UL Field Installed Accessory Kit for Use in Class I, Division 2, Groups A, B, C, and D
You can replace the I/O termination board in the field provided that the replacement has the exact
same part and version.
Restrictions
Hazardous area approvals request that any part replaced in the field be the exact same part ("like-
for-like"). Upgrading or substituting different parts violates hazardous area certification.
Refer to the table below for the correct field replacement part number.
Item
Flow Computer I/O Termination Board Field Installed Accessory Kit
for use with UL Listed Model Series FB2100 and FB220
Required Tools
Electrical Ratings
Ambient Temperature Ranges:
May be used up to a maximum ambient temperature of 80°C and a minimum ambient
temperature of –40°C; refer to the data plate attached to the device for ambient temperature.
EXPLOSION HAZARD – Substitution of any components may impair suitability for Class I,
Division 2.
EXPLOSION HAZARD – Do not disconnect equipment unless power has been removed or the
area is known to the non-hazardous.
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
#2 Phillips-head screwdriver
3/32-inch flat head screwdriver (For 3.81 mm pitch terminal block connections and
disconnecting the internal connector to the sensor)
Hexagonal torque wrenches with 3mm, #1, and #2 Phillips-head bits. Ranges must include 1
to 2 in-lbs (0.1 to 0.2 N-m), 4 to 6 in-lbs (0.5 to 0.7 N-m), and 10 to 12 in-lbs (.1 to 1.4 N-m).
Input Voltage: 10.5 Vdc to 30 Vdc external supply (Max power at 10 watts)
WARNING
WARNING
DANGER
D301805X012
November 2020
Field Replacement Kit
Part Number
400210010-KIT
1