Product Installation Guidelines
SERVICE AND MAINTENANCE
JUMPER VALVE TAPWARE
1. Turn off the water supply and turn on the tap handle
to drain water from the bodies.
2. Remove the temperature indicator from the handle.
3. Remove the handle from the tap.
4. Unscrew the top assembly from the body.
5. Check the o-ring on the spindle and the jumper
valve for wear and damage. Replace if required.
6. Clean the spindle and body of debris.
7. Place a new o-ring (if required) onto the spindle and
re-grease with potable water approved grease.
8. Re-assemble top assembly. Follow the product
installation guidelines for the relevant product to
re-assembly method.
TROUBLESHOOTING
PROBLEM
Taps are dripping
water
Water is leaking from
spindle
Spindle is difficult to
turn (jumper valve)
Handle is loose
Flange won't screw
down onto basin/sink
surface
© Galvin Engineering Pty Ltd
CAUSE
Jumper valves are worn or damaged
Ceramic discs are worn or damaged
O-ring on jumper valve spindle
is damaged or worn
Build up of scale on spindle, spindle
worn or o-ring has been damaged
Screw has come loose
Tap bodies are set too far out
CERAMIC CARTRIDGE TAPWARE
1. Turn off the water supply and turn on the tap handle to
drain water from the bodies.
2. Remove the temperature indicator from the
handle.
3. Remove the handle from the tap.
4. Unscrew the ceramic head part from the body.
5. Check the o-ring on the ceramic head part for
wear and damage. Replace if required.
6. Clean the head part and the body of any debris.
7. Replace the cartridge and screw tighten back into the
body.
8. Follow the product installation guidelines for the
relevant product to re-assemble.
RECTIFICATION
Replace jumper valve
Remove and inspect SBA. Remove debris
and/or replace SBA if damaged.
Replace o-ring
Remove jumper valve, clean and regrease. Replace
o-ring. Complete SBA may need to be replaced.
Tighten handle screw
Re-position tap bodies and breach piece
Document No.: 001.00.10.00
Version 1, 23 November 2021, Page 4 of 5