Gree XK47 Manuel du propriétaire - Page 15

Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} Gree XK47. Gree XK47 19 pages. Wired controller

Gree XK47 Manuel du propriétaire
Wired Controller XK41 & XK47

3.11 Other Functions

a. Lock
Upon startup of the unit without malfunction or under the "Off" state of the unit, press ▲ and ▼ at
the same time for 5s till the wired controller enters the Lock function. In this case, LCD displays
After that, repress these two buttons at the same time for 5s to quit this function.
Under the Lock state, any other button press won't get any response.
b. Memory
Memory switchover: Under the "Off" state of the unit, press Mode and ▲ at the same time for
5s to switch memory states between memory on and memory off. When this function is activated,
Memory will be displayed. If this function is not set, the unit will be under the "Off" state after power
failure and then power recovery.
Memory recovery: If this function has been set for the wired controller, the wired controller after
power failure will resume its original running state upon power recovery. Memory contents: On/
Off,Mode, set temperature, set fan speed and Lock function.

4 Installation and Dismantlement

4.1 Connection of the Signal Line of the Wired Controller

● Open the cover of the electric control box of the indoor unit.
● Let the single line of the wired controller through the rubber ring.
● Connect the signal line of the wired control to the 4-pin socket of the indoor unit PCB.
● Tighten the signal wire with ties.
● The communication distance between the main board and the wired controller can be up to
20 meters ( the standard distance is 8 meters)

4.2 Installation of the Wired Controller

PVC Pipe
No.
1
Socket box
Name
embedded
in the wall
Fig.4.1 Accessories for the Installation of the Wired Controller
2
Soleplate of
the Wired
Controller
1
Table 4.1
3
Front Panel
Screw
of the Wired
M4X25
12
2
3
4
4
Screw
ST 2.9X6
Controller
.
5
5