Gamewell MS-7S Mode d'emploi

Parcourez en ligne ou téléchargez le pdf Mode d'emploi pour {nom_de_la_catégorie} Gamewell MS-7S. Gamewell MS-7S 2 pages.

Description
The Gamewell-FCI MS-7 Style manual fire alarm stations
are available in a wide variety of configurations. The Sta-
tions comply with the Americans with Disabilities Act (ADA)
5-lb. maximum pull force requirement. Operating instruc-
tions and Braille text are engraved in the handle. All sta-
tions have a key lock/reset which is keyed alike with
Gamewell-FCI fire alarm control panels and other manual
fire alarm stations.
MS-7AF Velociti Addressable Station
®
The MS-7AF Velociti
Series addressable station is a dou-
ble action station designed for installation in the signaling
line circuit of Gamewell-FCI analog addressable control
panels. Activation of the station causes its assigned
address to register at the control panel. The door contains
an LED which flashes green in normal condition and lights
steady red when the station has been activated.* The sta-
tion features screw terminals.
MS-7ASF Velociti Addressable Station
®
The MS-7ASF Velociti
Series addressable station is a
single action station designed for installation in the signal-
ing line circuit of Gamewell-FCI analog addressable con-
trol panels. Activation of the station causes its assigned
address to register at the control panel. The door contains
an LED which flashes green in normal condition and lights
steady red when the station has been activated.* The sta-
tion features screw terminals.
®
The Velociti
Series stations use a communication proto-
col that substantially increases the speed of communica-
tion between the sensors and certain Gamewell-FCI
analog addressable fire alarm controls. These devices
operate in a grouped fashion. If one of the devices in the
group has a status change, the panel's microprocessor
stops the group poll and focuses on the single device. The
net effect is response speed up to five times greater than
earlier designs.
MS-7 Double Action Station
The MS-7 double action station is used with conventional-
fire alarm control panels. It features a set of single pole
contacts and screw terminals for connection to an initiating
circuit.
®
Velociti
is a registered trademark of Honeywell International Inc.
®
UL
is a registered trademark of Underwriter's Laboratories Inc.
®
LEXAN
is a registered trademark of GE Plastics, a subsidiary of General
Electric Company.
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2008 by Honeywell International Inc. All rights reserved.
Features
• Addressable stations compatible with all Gamewell-FCI
analog addressable fire alarm controls
• Conventional stations suitable for use with any UL
Listed control panel
• Both single and double action stations available
• Tumbler lock for test and reset keyed alike with
Gamewell-FCI controls
• Surface or semi-flush mounting
• Shock and vibration resistant
• Stations (MS-7LOB) Listed for outdoor applications
• Complies with ADA pull force requirements
Only the red LED is operative in panels that do not operate
in Velociti mode.
GAMEWELL-FCI
www.gamewell-fci.com
MS-7AF, MS-7
and MS-7S
Non-Coded, Manual
Fire Alarm Stations
MS-7
An ISO 9001-2000 Company
SIGNALING
FM
MEA
Approved
APPROVED
S2465
3023594
67-02-E Vol.VIII
07150-0694:261
9020-0616 Rev. B2 page 1 of 2
®