Programming

Alarms Latched
Alarms Not Latched
(Supervisory Alarms Only)
Class B
Class A

Power Requirements

Technical Manuals Online! - http://www.tech-man.com
Programming of the 31016 modules is accomplished with the INS-2 laptop software.
Each zone card installed requires 2 addresses regardless of wether both zones are
being used or not. The 31016 requires no programming of its address. It is addressed
automatically, via the ZNS, by its physical location to the addresses of 1 through 32.
Additional addressable modules may be added to the addressable circuits 1 and 2
starting with address 33.
JUMPER PROGRAMMING
Zone cards are shipped with all jumpers installed (Class B, Alarms Latched).
The ZNS common card draws 2 mA from the +24V supply and 5 mA from the
+5V supply.
The 31015 mother boards do not draw any power from the system.
Each 31016 zone card draws 0.5 mA from the +5V supply plus 6.5 mA for each
trouble or alarm LED on. Note that for one zone, the trouble and alarm LEDs will
never be on at the same time.
The current draw from the +24V supply for each zone on a 31016 zone card
depends upon whether it is configured for hi-current or low current operation.
lo-current -- without detect
lo-current -- in alarm
hi-current -- without detectors
hi-current -- with detectors
hi-current -- in alarm
firealarmresources.com
Odd Zone
W1L Installed
W1L Removed
W1A Installed
W1A Removed
2.5 mA max
6 mA max
6.5 mA max
9.1 mA max
60 mA max
3
Issue 4 12/4/98
Even Zone
W2L Installed
W2L Removed
W2A Installed
W2A Removed