HEAT DETECTOR MOD.: AE/C5-TV
The AE/C5-TV model is a rate of rise with fixed temperature detector. It provides an ambient temperature surveillance based on two operation
levels as follow:
Rate or Rise: In case of the ambient temperature increase sharply more than a prefixed value during a selected period of time the detector
will generate an alarm.
Fixed: When the ambient temperature is increasing slowly higher than a prefixed value, the detector will generate an alarm.
Each detector has two LEDs located in opposite side at the external assembly cover to inform to users by flashing about if the detector is in stand-
by operation or in permanent alarm as well. Remote LED annunciator capability is available upon request as an optional accessory to be wired to
the detector base terminals block.
This detector have a latching alarm feature. In case the detector in alarm function to move it to stand-by operation is requested to produce a
detector power supply switch-off from the remote fire alarm panel.
This detector model is manufactured and certified according to EN 54-7:2000 standard. Class A2R heat detector.
A heat detector will respond only when a fire is well established and generating a high heat output or where the environment is dirty or smoky
under normal conditions.
INSTALLATION GUIDELINES.
Mounting
The fixed base detector should be mounted directly onto an electrical junction box such as an octagonal (75mm, 90mm or 100mm), a round
(75mm) or a square (100mm) box without using any type of mechanical adapter.
Detectors loop wiring
Switch-off power supply to the detector's fixed base before plug-in any detector main frame to the fixed base.
Positive wire from detection loop shall be connected to the block terminal marked as 2 (loop input). The terminal block has double and
separate terminals marked as 2, one for loop input and the other one as loop output.
Negative wire from detection loop shall be connected to the block terminal marked as 5. The terminal block has double and separate
terminals marked as 5, one for loop input and the other one as loop output.
To built-up the detection loop to the next one detector or to the end of line proceed connecting by wire the free position 2 at the terminal
block with the position 2 (loop input) at the next one detector's block terminal or to the end of line. This procedure allows detection loop as
an open line operation type.
Proceed with negative wire in the same way as before mentioned for terminal block marked as 5.
In case it is required to install a remote LED annunciator, connections from annunciator will be made between its positive to terminal block 6
and negative to terminal block 3 at the base detector.