Airflow Duplexvent Flexi DV 2600 Manuel d'installation, d'utilisation et d'entretien - Page 7
Parcourez en ligne ou téléchargez le pdf Manuel d'installation, d'utilisation et d'entretien pour {nom_de_la_catégorie} Airflow Duplexvent Flexi DV 2600. Airflow Duplexvent Flexi DV 2600 19 pages. Ventilation units with
heat recovery
Également pour Airflow Duplexvent Flexi DV 2600 : Manuel d'installation, d'utilisation et d'entretien (18 pages)
Plan view - windowsill position
Window position:
The appliance is placed on height-adjustable feet (H
-
1600, 6 pcs in sizes 2600 and 3600).
Due to the condensate drain the appliance must be sloped toward section i2 (EHA).
-
Ceiling position:
The appliance is suspended from anchors of sufficient load bearing capacity (provided by the building contractor) using four
-
(sizes 1100, 1600 and 2600), and six (size 3600) suspension eyes (included in delivery) with Ø 11 mm holes.
Due to the condensate drain the appliance must be sloped toward section i2 (EHA), see the picture.
-
5.5 Adjusting the unit - turning ports e2 (SUP) / i2 (EHA)
●
Only units up to size 1600 can be adjusted that way.
●
When making the adjustment, follow the diagram below and the visual instructions in the appendix.
5.6 Connecting the condensate drain pipe
●
The unit is versatile and in total has 4 condensate outlets for 2 directions of air flow and 2 installation positions. A single specific
condensate outlet is always used for a particular application.
For the window position use the condensate outlet in section i2 (EHA)
-
DUPLEXVENT Flexi
1100
L (mm)
1700
= 147 mm) included in delivery (4 pieces in size 1100, 5 pcs in size
min
ℎ
1
ℎ
ℎ = 1,5
7
1600
2600
2020
2150
∆
=
+ 50 []
10
∆
=
+ 50 []
2
2 ∙ 10
∆
+ 100 []
10
3600
2450