When installina
two cookto~s.
use the
following
width dimension:'
'
Two
cooktops
I
Cutout
Width
I
-I
23" min
All other dimensions
remain the same
for all cutouts:
Cutout depth: 20-l/2"
Cutout to front of countertop:
l-1/2"
min.
Cutout to backsplash
or rear wall: l-1/2"
min.
Cutout to combustible
surface:
3-l/2"
Gas supply
requirements
Observe
all governing
codes and ordinances.
Explosion
Hazard
Use a new AGA approved
gas supply
line.
Install a shut-off
valve.
Securely
tighten
all gas connections.
If connected
to LP, have a qualified
person
make sure gas pressure
does not exceed
14" water column.
Examples
of a qualified
person include
licensed
heating
personnel,
authorized
gas company
personnel,
and
authorized
service
personnel.
Failure to do so can result in death,
explosion,
or fire.
IAl
This installation
must conform with state
or other codes or, in the absence of
. such codes, with the Standard for
Recreational
Vehicles, ANSI Al 19.2.'*
Copies of the standards
listed may be obtained
from:
* National
Fire Protection
Association
Batterymarch
Park
Quincy,
Massachusetts
02269
IBI
Input ratings shown on the model/serial
. rating plate are for elevations up to
2,000 feet. For elevations above 2,000
feet ratings are reduced at a rate of 4% for each
1,000 feet above sea level.
El
Provide a gas supply line of 3/4" rigid
. pipe to the cooktop location. A smaller
size pipe on long runs may result in
insufficient gas supply. Pipe-joint compounds
made for use with L.P. gas must be used.
IDI
If local codes and ordinances permit,
n
A.G.A.-design-certified,
new flexible
metal tubing is recommended for
connecting cooktop to the gas supply line. Do Not
kink or damage the flexible tubing when moving
the cooktop. A l/2" male pipe thread is needed
for connection to pressure regulator female pipe
threads.
shutoff
valve
El
The supply line shall be equipped with
. an approved shutoff valve. This valve
should be located in the same room as
the cooktop and should be in a location that
allows ease of opening and closing. Do Not block
access to shutoff valve. The valve is for turning
on or shutting off gas to the appliance.
IF'
If rigid pipe is
L-l usedasagas
n
n
supply line, a
combination
of pipe
fittings must be used to
obtain an in-line
connection to the cook-top. All strains must be
removed from the supply and fuel lines so
cooktop will be level and in line.
El
The regulator must be checked at a
. minimum 1" water column above the set
pressure. The inlet pressure to the
regulator should be a s follows for operation and
checking the regulator setting:
L.P. GAS:
Set pressure
10 inches W.C.
Maximum
pressure
14 inches W.C.
4