Electronic Circuit Protector ESX10-T.-DC 24 V
Technical data (T
= 25 °C, U
amb
Reset signal RE
with the falling edge of a + DC 24 V
terminal 22
pulse the electronically blocked
ESX10-TB-124/-127 can be reset via an
external momentary switch. A joint reset
signal can also be applied to more than
one device at a time. Devices in ON
condition will remain unaffected.
Control input I
+
ESX10-T-114
N
Electrical data
as reset input RE
Control signal I
+
+24 V level (HIGH): device is switched on
N
by a Terminal 21
remote ON/OFF signal.
0 V level (LOW) device is switched off by
a remote ON/OFF signal.
Switch S1 ON/OFF
device can only be S1 switched on when
a HIGH level is applied to I
+
N
LED indication
ON:
OFF:
General data
Fail-safe element
back-up fuse for ESX10-T not required,
due to an integral redundant fail-safe
element (protective element)
Terminals
LINE+ / LOAD+ / 0V
screw terminals
max. cable cross section
rigid and flexible
flexible with wire end ferrule w/wo
plastic sleeve
stripping length
tightening torque (EN60934)
multi-lead connection
(2 identical cables)
rigid / flexible
flexible with wire end ferrule
without plastic sleeve
flexible with TWIN wire end ferrule
with plastic sleeve
Terminals
signal terminals
Screw terminals
max. cable cross section
flexible with wire end ferrule w/wo
plastic sleeve
stripping length
tightening torque (EN60934)
Housing material
moulded
Mounting
symmetrical rail to EN 60715-35x7.5
Ambient temperature
-25...60 °C
(without condensation, cf. EN 60204-1)
1)
ambient temperature range can differ
depending on approvals.
Storage temperature
-40...70 °C
Humidity
96 hrs / 95% RH 40°C to
IEC 60068-2-78, test Cab
climate class 3K3 to EN60721
Vibration
3g test to IEC 60068-2-6, test Fc
Protection class
housing IP20 EN60529
terminals IP20 DIN 60529
1822
= DC 24 V)
B
LED green
LED red
M4
0.5 - 16 mm
2
0.5 mm – 10 mm
2
10 mm
1.5 - 1.8 Nm
2
0.5 – 4 mm
0.5 – 2.5 mm
2
0.5 – 6 mm
2
M3
0.25 – 2.5 mm
2
8 mm
0.5 - 0.6 Nm
1)
www.e-t-a.de
Technical data (T
= 25 °C, U
amb
EMC requirements
noise emission EN 61000-6-3
(EMC directive, CE marking) noise immunity: EN 61000-6-2
Insulation co-ordination
0.5 kV / pollution degree 2
(IEC 60934)
reinforced insulation at operating area
Dielectric strength
max. DC 32 V (load circuit)
Insulation resistance
n/a, only electronic disconnection
(OFF condition:)
Conformity
CE marking
to 2014/30/EU
Dimensions (w x h x d)
12.5 x 80 x 83 mm
Mass
approx. 65 g
= DC 24 V)
B
4
3