Fujitsu ABU18RULX Spécifications - Page 12
Parcourez en ligne ou téléchargez le pdf Spécifications pour {nom_de_la_catégorie} Fujitsu ABU18RULX. Fujitsu ABU18RULX 30 pages. Floor console / under ceiling dual type
Également pour Fujitsu ABU18RULX : Manuel (48 pages)
- 1. Table of Contents
- 2. Specifications
- 3. Outline and Dimensions
- 3. Outdoor Unit
- 3. Indoor Unit
- 4. Refrigerant System Diagram
- 5. Circuit Diagram
- 6. Pcb Circuit Diagram
- 6. Outdoor Pcb Circuit Diagram
- 6. Error Contents
- 7. DISASSEMBLY ILLUSTRATION (Indoor Unit) DISASSEMBLY ILLUSTRATION (Outdoor Unit)
- 8. PARTS LIST (Indoor Unit)
- 9. Remote Control Unit
- 10. PARTS LIST (Outdoor Unit)
ERROR CONTENTS
(Indoor unit)
Operation can be checked by lighting and flashing of the display section OPERATION,
TIMER, and VERTICAL SWING lamps.
Perform judgment in accordance with the following.
TEST RUNNING
When the air conditioner is run by pressing the remote control unit test run button, the
OPERATION, TIMER, and VERTICAL SWING lamps flash slowly at the same time.
ERROR
The OPERATION, TIMER, and VERTICAL SWING lamps operate as follows (Table 1)
according to the error contents.
OPERATION
lamp (RED)
(2 times)
(2 times)
(3 times)
(3 times)
(4 times)
(5 times)
(5 times)
(6 times)
2005.12.28
SWING
SWING
TIMER
OERATION
TIMER lamp
SWING lamp
(GREEN)
(ORANGE)
(2 times)
(3 times)
(3 times)
(4 times)
(4 times)
(5 times)
(5 times)
(6 times)
(7 times)
: 0.1s ON/0.1s OFF (flash)
: 0.5s ON/0.5s OFF (flash)
VERTICAL SWING lamp (Orange)
TIMER lamp (Green)
OPERATION lamp (Red)
MANUAL
AUTO
Error contents
Indoor EEPROM abnormal
Outdoor EEPROM abnormal
Indoor room temperature sensor open
Indoor room temperature sensor shortcircuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor shortcircuited
Float switch operated
Indoor signal abnormal
Outdoor signal abnormal
Indoor fan abnormal
Outdoor power source connection abnormal
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor shortcircuited
Outdoor temperature sensor open
Outdoor temperature sensor shortcircuited
Outdoor discharge pipe temperature sensor or compressor
temperature sensor open
Outdoor discharge pipe temperature sensor or compressor
temperature sensor shortcircuited
Outdoor high pressure abnormal
Outdoor discharge pipe temperature or compressor
temperature sensor abnormal
: OFF
11