Chapter 1
ETERNUS DX Installation
1.7
Outlet/Socket Specifications
●
For Direct (No Power Distribution Unit) Connection
The following diagram shows a power supply connection example when no power distribution units are used.
Figure 1.11 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used
CP
PSU:
Power Supply Units
CP:
Circuit Protector
1.7.4
Input Power Supply Lines
Multiple power supply facilities in the building or multiple UPS units are recommended for power supply re-
dundancy. A redundant configuration is used for the power supply of the ETERNUS DX. Business can continue
even if one of the power supply lines fails.
However, a single power supply facility configuration is also allowed for the entire system optimization (in-
cluding the server). When selecting a single configuration, take into consideration the availability of the sys-
tem.
Figure 1.12 Dual-Line Power Supply (When Connecting to Power Sockets)
Line 1
Line 0
ETERNUS DX
Drive enclosure
Controller
enclosure
Line 0
Do
Only connect the ETERNUS DX to circuit protectors.
•
Power distribution unit
ETERNUS DX
PSU
PSU
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
CP
Line 1
29