Kohler 15REYG Fonctionnement - Page 18
Parcourez en ligne ou téléchargez le pdf Fonctionnement pour {nom_de_la_catégorie} Kohler 15REYG. Kohler 15REYG 40 pages. Commercial generator sets
Code Fault
AF
Auxiliary fault
input shutdown
HE
High engine
temperature
shutdown
LCL
Low coolant
level
LOC
Loss of coolant
LOP
Low oil
pressure
shutdown
OC
Overcrank
shutdown
OF
Overfrequency
shutdown
OS
Overspeed
shutdown
OU
Overvoltage
shutdown
UF
Underfrequency
shutdown
UU
Undervoltage
shutdown
SCF0 Software
Communication
Fault 0
Figure 2-4 ADC 2100 Fault Shutdown Codes
18
Section 2 Operation
Description
Input from a customer-supplied switch that
closes when the fault is active. The generator
set shuts down 0.3 seconds after the fault is
detected and will not start when the fault is
active (input is grounded). This protection
becomes active 3 seconds after crank
disconnect.
Shutdown occurs if the engine coolant
temperature exceeds the maximum temperature
for more than 5 seconds. This protective
becomes active after the engine reaches the
crank disconnect speed.
Not used.
Not used.
Shutdown occurs if a low oil pressure condition
exists for more than 5 seconds. This protective
becomes active 30 seconds after the engine
has reached crank disconnect speed
(30 second inhibit).
Shutdown occurs after 3 unsuccessful starting
attempts. The crank cycle is set for three
starting attempts of 15 seconds cranking and 15
seconds rest.
The generator set also shuts down if no engine
rotation is sensed during cranking. Shuts down
1 second after the fault is detected.
Shutdown occurs when the governed frequency
exceeds 110% of the system's frequency
setpoint for more than 5 seconds. This
protective becomes active 10 seconds after
engine start (10 second inhibit).
Shutdown occurs if the engine speed exceeds
115% of the normal running speed for more than
0.3 seconds.
Shutdown occurs if the voltage exceeds 120%
of the system nominal voltage for more than 2
seconds.
Shutdown occurs when the governed frequency
falls below 90% of the nominal system
frequency for more than 5 seconds or below 59
Hz for more than 60 seconds. This protective
becomes active 10 seconds after engine start.
(10 second inhibit).
Shutdown occurs if the voltage falls below 80%
of the nominal system voltage for more than 10
seconds.
Indicates a software or communication problem
within the ADC 2100
Check
Check the cause of the auxiliary fault.
Check for blocked air inlets and exhaust outlets.
—
—
Check for leaks in the lubrication system.
Check the oil level and add oil if the level is low.
Check the fuel supply, spark plug, and battery.
Check for loose connections.
Contact an authorized distributor/dealer for
service if problem continues.
Contact an authorized distributor/dealer for
service if problem continues.
Contact an authorized distributor/dealer for
service if problem continues.
Contact an authorized distributor/dealer for
service if problem continues.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for
service if problem continues.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for
service if problem continues.
Replace the controller.
TP-6728 10/11