Kohler 20RESC Manuel d'installation et d'utilisation - Page 24
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} Kohler 20RESC. Kohler 20RESC 37 pages. Residential/commercial generator sets
Également pour Kohler 20RESC : Instructions d'installation (2 pages), Fonctionnement (20 pages)
Fault Text
Description
LossOfField
This generator has absorbed more than 25% reactive
power (magnetic excitation current) for 20 seconds
BusDeadLive
The Bus is measured to be dead when one of the
generators is supposed to be supplying voltage to the
bus (closed contactor)
BusLiveDead
The Bus is measured to be live when no generators
are connected to it (both contactors open).
Figure 23 Other Events
24
Possible Causes
Generator voltage on this generator is not
calibrated correctly.
Generator voltage on other generator is
not calibrated correctly.
Bus voltage on this generator is not
calibrated correctly.
Bus voltage on the other generator is not
calibrated correctly.
Bus metering V9A and V9B connections
to V9 of paralleling protection harness are
connected incorrectly.
Bus metering V9A and V9B connections
to V9 of paralleling protection harness
connected incorrectly.
TT-1596
8/22