Kohler DC2 Manuel d'installation - Page 25

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Kohler DC2. Kohler DC2 44 pages. Residential/commercial generator sets
Également pour Kohler DC2 : Manuel d'installation (48 pages), Fonctionnement (20 pages)

Kohler DC2 Manuel d'installation
Generator Set
Generator Set Terminal Block TB1.
See Figure 1-6 for location. Check the
decal on the generator set for terminal block
connections.
Note: See Figure 1-21 for maximum total cable length
per run (1 run shown).
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
Figure 1-22 Accessory Module Communication Connection Details
TP-6803 12/11
Connect one end of each cable shield
to GROUND at the generator set.
GND
A
A
RBUS
B
B
PWR
PWR
12 VDC
COM
COM
4
3
TB1
Connect shields together
as shown.
1
RXT
A
B
PWR
COM
PIM
A
B
PWR
COM
A
B
PWR
COM
Leave one end of each cable shield
disconnected at the last device.
A
B
PWR
COM
A
B
PWR
COM
LCM
Section 1 Installation
25