AB Quality GuardPLC 1800 Manuel d'instructions d'installation - Page 14

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} AB Quality GuardPLC 1800. AB Quality GuardPLC 1800 20 pages.

14
GuardPLC™ 1600 Controllers
Digital Output Terminals
Terminals accommodate wires up to 1.5 mm
connected to the following terminals:
Terminal Number
1
2
3
4
5
6
7
8
9
10
11
12
For connection of a load, the reference pole L- of the concerned channel group
must be used (2-pole connection). Although L- at terminals 1 and 6 and at 7 and 12
is connected internally to L- on the power supply input, it is strictly recommended
to use 1 and 6 for outputs 1 through 4 only and 7 and 12 for outputs 5 through 8
only. EMC testing was performed in this manner.
Publication 1753-IN001B-EN-P - March 2004
1 2 3 4 5 6
1 2 3 4
5 6
DO
L-
1
2
3 4
L-
(2A)
Designation
Function
L-
Reference pole
1
Digital output 1
2
Digital output 2
3
Digital output 3
4
Digital output 4 (for increased load)
L-
Reference pole
L-
Reference pole
5
Digital output 5
6
Digital output 6
7
Digital output 7
8
Digital output 8 (for increased load)
L-
Reference pole
7 8 9 10 11 12
7 8 9 10
11 12
DO
L-
5
6
7 8
L-
(2A)
2
(16 AWG). Digital outputs are
Current
0.5 A
0.5 A
0.5 A
2.0 A
0.5 A
0.5 A
0.5 A
2.0 A