CP Electronics MWS3A-DD Manuel du produit - Page 6
Parcourez en ligne ou téléchargez le pdf Manuel du produit pour {nom_de_la_catégorie} CP Electronics MWS3A-DD. CP Electronics MWS3A-DD 12 pages. Direct dim microwave presence/absence detector
Également pour CP Electronics MWS3A-DD : Manuel d'installation (20 pages)
9. Programming
All the following functions can be programmed using the remote control DD-LCDHS handset:
1.
Detector Parameters (factory default in brackets):
1.1 Time adjustment
1.2 Sensitivity On (9)
1.3 Sensitivity Off (9)
1.4 Power Up On (Y)
1.5 Walk Test (N)
1.6 Disable Detector (N)
1.7 Factory Default
2.
Modes (factory default in brackets):
2.1 Channel Modes
2.1.1 Switch only
2.1.2 Switch and dim together (default)
2.1.3 Switch and dim separate
2.2 Switch Modes
2.2.1 2 position switch together (default) A single centre biased retractive switch will be used to
2.2.2 2 position switch separate
2.2.3 1 position switch together
2.2.4 1 position switch separate
3.
Switching Channel 1 functions (factory default in brackets):
3.1 Presence detection
3.2 Absence detection
3.3 Switch level on (9)
3.4 Switch level off (9)
page 6
10 seconds to 99 minutes time delay (select 0 for 10 second
delay – use for commissioning only).
Sensitivity level when the detector is already operational
adjustable between 1 (min.) and 9 (max.)
Sensitivity level for switching the detector on – adjustable
between 1 (min.) and 9 (max.).
Select No for a 30 second delay on start up. If Yes is selected,
there will be no delay on start up and the detector will always
power up detecting.
An LED behind the detector lens will flash to show movement
has been detected (use for commissioning).
Disables detection, leaving the relay output permanently off
with the dimming output operational. This mode is used when
the unit is for maintained illuminance only.
Restores factory default settings.
Usually used for absence detection - in this mode the dimming
channel is not used.
The detector will switch and dim the lighting together.
Provides 2 channel operation – Channel 1 is switched via the
relay output, and Channel 2 is dimmed / switched via the
dimming output.
control both channels together.
A single centre biased retractive switch will be used to
control only the dimming channel.
A single position retractive switch controls both channels
together.
Two single position retractive switches, controlling the
channels separately.
Auto switch on with detection, auto off after movement ceases
(MWS3A-DD default) and time delay ends.
Manual switch on, auto off after movement ceases and time
(MWS3A-DD/ABS default) delay ends.
Lux level setting to prevent the luminaires being switched on if
the ambient light level is sufficient (adjustable between 1
and 9). The luminaires will always be switched on at level 9.
For a higher resolution of ‗switch level on' a scale of 101-199
is available in the ‗Special menu'.
Lux level setting to switch the luminaires off during occupancy
if the ambient light level goes above the setting (adjustable
between 1 and 9). Level 9 will always keep the lights on. This
setting can be used for ―window row switching‖.
For a higher resolution of ‗switch level off' a scale of 101-199
is available in the ‗Special menu'.