CP Electronics MWS5 Manuel du produit - Page 7
Parcourez en ligne ou téléchargez le pdf Manuel du produit pour {nom_de_la_catégorie} CP Electronics MWS5. CP Electronics MWS5 12 pages. Miniature ceiling mounted microwave presence detector
Settings adjustment:-
On initial power up, the factory set default settings are:-
Presence Detection mode.
Time = 20 minutes.
Lux = Maximum (i.e. lights will switch on in full daylight on detection).
Sensitivity = Maximum.
Presence or Absence detection mode
The unit ships with presence detection as default.
To check the mode press and hold both buttons together: after 3 seconds the green LED lights up —
leave the buttons pressed. After a further 3 seconds the following LED's will light:
Green/Yellow = Presence Detection mode
Green/Red = Absence detection mode
To accept the current mode release the buttons immediately.
To change the mode keep the buttons pressed for another 5 seconds until the LED's change, then
release.
Time
All versions — set the time period using the push button adjustment overleaf or the programming
handset (see section 6). The factory default is 20 minutes.
Lux
MWS5 (Non-dimming) — the switch level on lux setting determines the ambient light level at which the
lights turn on. This can be set using the push button adjustment overleaf or the programming handset (see
section 6). Setting to maximum (level 7) ensures that lights always come on (this is also the default
setting).
-DD & -AD (Dimming) — switch level on described above is available using the programming handset
only. The push button lux adjustment determines the dimming output level and can be set using push
button the programming handset light level and works as follows:
During operation the output level varies very gradually. However when the level is
changed the unit automatically enters setup mode: in this mode the output level varies
rapidly. After the setup time the unit reverts to normal.
When adjusting, allow the output level to settle by changing very gradually.
To disable the maintained illuminance function completely, set the level to maximum.
User handset
Using the UHS or UHS3 infra-red handset: the override on button turns the unit on permanently; the
override off button turns the unit off permanently; the cancel button cancels the overrides. When an
override is selected an LED will flash inside the unit. The UHS handset can also be used to set the lux
levels (see section 5).
4. Setup cont.