Comments on the energy efficient control
(Overflow and economy mode)
The most original concept of the AS Control Plus is the tempera-
ture-dependent switching between overflow and economy (also
known as normal operation) modes of operation and the resultant
energy savings.
1. Overflow operation:
In the so-called overflow operation (normal operation) the water is
circulated via the overflow channel ➔ overflow tank ➔ pump
➔ pool ➔ overflow channel. The hydraulic operation is optimal
because the pool water is drained via the overflow. However, with
high water temperatures and low air temperatures there is a large
amount of heat loss (evaporation, convection). During operation,
with the pool covered open, the pool water has to be circulated
via the overflow.
2. Economy mode:
In so-called economy mode water is drained directly from the pool
(i.e. from one or more drains). Pool ➔ pump ➔ pool. Thus the
water no longer flows via the overflow. The heat loss is reduced
considerably. Economy mode is best suited to periods of cold
weather or during a pool heat-up period. During periods of use
the pool should always be run in overflow mode for reasons of
security and hydraulic efficiency.
Limits of liability:
We do not assume any liability for the layout or safety of the
drainage system. The correct layout of the drainage system is the
responsibility of the installation company. The local regulations
concerning the safety of drainage systems must be observed.
If there are no specific regulations we always recommend that
drains with hair-trap security be fitted. As well as installing at least
two drains with a distance of 1,5 m between them. The suction
speed of the drains should not exceed 1,2 m/s. The ideal position
for drains is where the bathers cannot come into contact with them.
CAUTION: incorrect drain installation can cause death.
Pump switched off:
If the pump is switched off or there is an electricity cut, the
Besgo valve will be in economy mode (drain directly from the
pool). In this way the pool will not be emptied by mistake. The
water cannot be fed back into the overflow tank via jets and the
filter. That would lead to a loss of water, if the water level in the
collection tank were to rise so high that the water flowed over
the edge of the buffer tank.
As additional security we recommend the installation of a
non-return valve into the inlet jet system as well as the
incorporation of a forced start (5th probe) in the collection
tank.
Limits of liability:
We do not assume any liability for the cost of loss of water, which
is caused by the failure, and/or misuse of the AS Control Plus or
the Besgo valves.