DGF Fabrications N2 Manuel d'installation et d'entretien - Page 12

Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'entretien pour {nom_de_la_catégorie} DGF Fabrications N2. DGF Fabrications N2 14 pages. Gas effect fires (natural gas & lpg) for decorative purposes only

1. This fire should be serviced every 12 months to ensure safe operation
2. Spares are available from the manufacturer.
3. The fire may a odour/smell given off when first lit for the first few hours. This is due to the newness of
the components and will cease in a few hours of burning.
4. Chimney should be checked annually to ensure continuing clearance of combustion products.
Hands should be washed after handling coals
5.
6. Open fires are a hazard; it is recommended that a guard be fitted to provide protection for children, the
elderly, the infirm and pets. (see National Regulations, if any)
7. All debris and soot should be cleaned with a soft brush when appliance is cold.
8. Regular checks must be made to check the fixed air supply (if applicable) is free of any obstructions.
Note. Seek expert advice if you are unsure of any points regarding the safe use of this appliance.
No Spark
Pilot light damaged, or too far away from electrode, or too close
Electrode retaining lock nut has become too loose. Needs to be tightened
Ignition lead has become detached from electrode. Re-connect it
Electrode is damaged. Replace.
Soot on the pilot assembly and shorting spark. Clean with soft brush
Faulty ignition lead. Replace.
Spark is visible but pilot will not light
Check there is gas getting to appliance
Ensure that isolating valve or restrictor elbow is in the open position
Valve inlet has become blocked with debris. Clean with soft brush.
Pilot injector is blocked. Clean with soft brush.
Pilot Flames shortens / goes out, when main burner is selected
This indicates insufficient gas pressure to the appliance. Check for debris or obstruction.
Check that there are no acute bends in the supply pipe and ensure that the correct diameter supply pipe
has been used.
Check pressure setting.
Note. If the appliance has been connected to a supply servicing another appliance the supply pipe may
not have sufficient capacity to serve both appliances. Seek advice.
Make sure enough air can circle around the pilot.
Units 1-3 Vulcan St, Edward St Industrial Estate, Darlington. DL1 2UL – Tel: 01325 281304; Fax: 01325 481889

SPECIAL NOTES

TROUBLE SHOOTING
12
DGF Fabrications;