FILTER MAINTENANCE - the CR SERIES is equipped with a 100 mesh screen
filter. This filter should be checked periodically. A partially clogged filter will
slow down the recovery rate of this unit.
Replace the filter cartridge as follows:
1.
Use a 7/8" socket or boxed end wrench to loosen the suction port as shown
in Figure 1.
2.
Once loose, remove the suction port- filter cartridge assembly is shown in
.
Figure 2
3.
Either clean the current cartridge or replace with new cartridge.
(Item NO. CRXF3)
4.
Inspect O-RING. RE-LUBRICATE with compressor oil or equivalent.
5.
Place filter back into suction port fitting.
6.
Hand tighten this assembly back onto the CR unit.
7.
Use a 7/8" socket or boxed end wrench to tighten 1/8 of a turn. DO NOT
OVER TIGHTEN, damage to the O-RING may occur.
8.
Check the connection for leaks.

ROUTINE MAINTENANCE

Figure 1
Figure 2
6