Dell 6100 Installation du rack - Page 22
Parcourez en ligne ou téléchargez le pdf Installation du rack pour {nom_de_la_catégorie} Dell 6100. Dell 6100 34 pages. Dell poweredge 4200 servers: installation guide
Également pour Dell 6100 : Installation du rack (37 pages), Manuel complémentaire (4 pages), Manuel du matériel (15 pages)
(Rev. 9/8/00) FILE LOCATION: S:\SYSTEMS\MARCONI\Rackingd\7U\05KCEa00\05KCEeb0.fm
8
Rack Installation Guide
Installing the Slide Assemblies in the Rack
You must allow 7 U (12.25 inches) of vertical space for each PowerEdge system you
install in the rack.
The rails of the rack are marked by small indentations in 1-U increments (see
Figure 6).
1 U (1.75 inches)
Figure 6. One Rack Unit
For more information, see the Dell Rack Advisor software available on the Dell World
Wide Web site at http://support.dell.com.
WARNING: If you are installing more than one computer, install the slide
assemblies so that the first computer is installed in the lowest available
position in the rack.
To determine where to install the slide assemblies in the rack, perform the following
steps:
1.
Place the front of the template over the front rack rails (see Figure 7).
The printing on the template identifies the side facing outward as the template
front.
2.
Position the bottom of the template where the system's lower edge will be
located.
DELL CONFIDENTIAL - Preliminary
9/8/00