Dell PowerVault MD1000 Information Update - Page 5

Parcourez en ligne ou téléchargez le pdf Information Update pour {nom_de_la_catégorie} Dell PowerVault MD1000. Dell PowerVault MD1000 42 pages. Dl backup to disk appliance - powered by commvault
Également pour Dell PowerVault MD1000 : Manuel de la matrice de soutien (11 pages), Manuel de référence (35 pages), Matrice de soutien (21 pages), Information Update (18 pages), Manuel complémentaire (2 pages), Diagramme de configuration (2 pages)

Dell PowerVault MD1000 Information Update
Additional Information for Troubleshooting a
SAS/SATA drive
Reseating a drive during initial set up is a valid step. If an enclosure is in
production and if there are no problems other than non-detection of a drive,
replace the drive that is not detected rather than reseating the drive.
It is recommended not to reseat a SMART tripped or failed drive. You cannot
reset a SMART tripped drive back to normal state. If a drive fails due to the
controller, check if a new firmware is available to fix the issue. If a firmware
update does not fix the issue, replace the drive.
NOTE:
If an amber blink sequence represents a SMART trip, the drive must be
replaced. It cannot be fixed by a firmware update.
For more information about troubleshooting a SAS/SATA drive, see the Dell
PowerVault MD1000 Storage Enclosure Hardware Owner's Manual at
support.dell.com/manuals.
Troubleshooting Enclosure Problems
Problem
One of the temperature probes displays an abnormal temperature reading.
Action
The system management software displays four temperature probes (0-3).
Probe 0 represents the temperature sensor on enclosure management module
(EMM) 0. Probe 1 represents the temperature sensor on EMM1. Probe 2 and
3 are temperature sensors on the midplane.
To resolve this issue:
Check for airflow obstruction.
Replace the component with the abnormal temperature sensor.
NOTE:
The power supplies do not have a temperature sensor that reports to the
system management software.
Information Update
5