INSTALLATION, OPERATION, AND MAINTENANCE
Testing
Perform testing in accordance with the procedure described in the checklist.
Duplex Pump Startup and Test Checklist
`
1
Power to control panel
2
Power to pump
3
Initial display is accurate
4
Pump Manual mode start and display
5
Pump suction PSI at static run
6
Pump discharge PSI at static run
7
Pump Man mode disable on leak
8
Pump Man mode disable on estop
9
Set Filter Cycle for 1 Min ON and 1 Min OFF
10
Set Pump to AUTO mode
11
Select Filter Cycle Manual mode
12
Confirm pump start and run for 1 Mi
13
Confirm pump stop after 1 Min
14
Select OFF then MAN and confirm 1 Min recycle
15
Pump Auto mode disable on leak
16
Pump Auto mode disable on estop
17
Select Filter Cycle Auto mode
18
Confirm pump start and run for 1 Min
19
Confirm pump stop after 1 Min
20
Confirm 1 Min OFF cycle
21
Confirm recycle
Simulate DP or High Pressure input and display
20
Simulate High Water input and display
21
Confirm Output Relay on Active
22
Confirm Output relay and horn on Alarm
23
Alarm modes: Leak, DP, Water
Model M300
Filtration Polisher
EMERGENCY POWER FUEL SYSTEMS
12 of 16
earth safe
Fuel Systems for Critical Power