ABB ACS880-01 Series Manuel d'installation et de démarrage rapide - Page 15

Parcourez en ligne ou téléchargez le pdf Manuel d'installation et de démarrage rapide pour {nom_de_la_catégorie} ABB ACS880-01 Series. ABB ACS880-01 Series 17 pages. Industrial drives
Également pour ABB ACS880-01 Series : Manuel d'installation (20 pages), Manuel d'installation rapide (14 pages), Manuel (16 pages), Manuel de l'utilisateur (18 pages)

ABB ACS880-01 Series Manuel d'installation et de démarrage rapide

Ambient conditions

Installation altitude
Surrounding air temperature
Safe torque off (STO)
The drive has a Safe torque off function (STO) in accordance with IEC/EN 61800-5-2. It can be used, for example, as the final
actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit).
When activated, the STO function disables the control voltage of the power semiconductors of the drive output stage, thus
preventing the drive from generating the torque required to rotate the motor. The control program generates an indication
31.22
as defined by parameter
activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation.
The safety data given in this manual is calculated for redundant use, and does not apply if both channels are not used.
WARNING! The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.
Notes:
If stopping by coasting is not acceptable, stop the drive and machinery using the appropriate stop mode before
activating the STO.
The STO function overrides all other functions of the drive.
Wiring
The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the
switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.
Validation
To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent
person with adequate expertise and knowledge of the safety function. The test procedures and report must be
documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware
manual.
Technical data
Minimum voltage at IN1 and IN2 to be interpreted as "1": 17 V DC
STO reaction time (shortest detectable break): 1 ms
STO response time: 2 ms (typical), 5 ms (maximum)
Fault detection time: Channels in different states for longer than 200ms
Fault reaction time: Fault detection time + 10ms
STO fault indication (parameter
STO warning indication (parameter
Safety integrity level (EN 62061): SIL 3
Performance level (EN ISO 13849-1): PL e
The drive STO is a type A safety component as defined in IEC 61508-2.
For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual
Markings
The applicable markings are shown on the type designation label of the drive.
CE
UL

Related documents

Document
ACS880-01 hardware manual
ACS880 primary control program firmware manual
ACx-AP-x assistant control panels user's manual
Drive composer PC tool user's manual
Converter module capacitor reforming instructions
0 ... 4000 m (0 ... 13123 ft) above sea level. The output current must be derated at
altitudes above 1000 m (3281 ft). The derating is 1% for each 100 m (328 ft) above
1000 m (3281 ft).
TN (grounded) and IT (ungrounded) systems.Installing on 525...690 V corner-grounded
or midpoint-grounded delta systems is not allowed.
Operation: -15 ... +55 °C (5 ... 131 °F). Frost is not permitted. The rated output current
must be derated by 1% for each 1 °C (1.8 °F) over 40 °C (104 °F) for IP21 (UL Type 1) drives
and for IP55 (UL Type 12) frames R1...R7 (for frames R8 and R9, see the hardware
manual). Storage (in the package): -40 to +70 °C (-40 to +158 °F).
. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the
31.22
) delay: < 500 ms
31.22
) delay: < 1000 ms
RCM
EAC
EIP green
WEEE
TÜV Nord
15
CSA
UKCA
Code (English)
3AXD50000078093
3AXD50000085967
3AUA0000085685
3AUA0000094606
3BFE64059629