ABB ACS880-01 Series Manuel d'installation et de démarrage rapide - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et de démarrage rapide pour {nom_de_la_catégorie} ABB ACS880-01 Series. ABB ACS880-01 Series 17 pages. Industrial drives
Également pour ABB ACS880-01 Series : Manuel d'installation (20 pages), Manuel d'installation rapide (14 pages), Manuel (16 pages), Manuel de l'utilisateur (18 pages)
motors and 1000 V AC for 480 V AC and 600 V AC motors. 600 V AC for 230 V AC and 480 V AC power lines; 1000 V AC
for 600 V AC power line.
•
Temperature rating: IEC installations: Select a cable rated for at least 70 °C maximum permissible temperature of
conductor in continuous use. NEC installations: Use 75 °C conductors minimum. Insulation temperature can be
higher as long as the ampacity is based on 75 °C conductors.
•
Select the control cables.
•
Use double-shielded twisted-pair cable for analog signals. Use double-shielded or single-shielded cable for the
digital, relay and I/O signals. Do not run 24 V and 115/230 V signals in the same cable.
•
Protect the drive and input power cable with the correct fuses. See
4. Examine the installation site
Examine the drive installation site. Make sure that:
•
The installation site is sufficiently ventilated or cooled to remove heat from the drive.
•
The ambient conditions of the drive meet the specifications. See
•
The wall behind the drive and the material above and below the unit is of non-flammable material.
•
The installation surface is as close to vertical as possible and strong enough to support the drive.
•
There is sufficient free space around the drive for cooling, maintenance and operation. For the minimum free space
Dimensions, weights and free space requirements
requirements, refer to
•
There are no sources of strong magnetic fields such as high-current single-core conductors or contactor coils near the
drive. A strong magnetic field can cause interference or inaccuracy in the operation of the drive.
5. Install the drive on the wall
Select fasteners that comply with local requirements applicable to wall surface materials, drive weight and application.
R1...R4 (IP21, UL Type 1)
1
× 4
R5...R9 (IP21, UL Type 1)
200 mm
(7.87")
a
2
1
300 mm
(11.81")
(IP55, UL Type 12) R1...R9
200 mm
(7.87")
a
1
2
300 mm
(11.81")
R1
R2
mm
in
mm
in
a
98
3.85
98
3.85
b
358 14.09 358 14.09 451
c
-
-
-
× 4
2
3
4
R5
4
3
R3
R4
mm
in
mm
in
125
4.92
160
6.30
17.75
505
19.88
-
-
-
475
18.70
Ratings, fuses and typical power cables
Ambient conditions
.
R4: × 6
3
2
R1...R3:
6 (.23)
1 1 (.45)
4
R4:
7 (.26)
13 (0.51)
9 (.35)
5
7
8
R5
R6
mm
in
mm
in
160
6.30 212.5 8.37
612
24.10
571 22.50 623 24.53 701
581
22.87
531
20.91 583 22.95 658 25.91 658 25.91
.
.
7 (.26)
13 (0.51)
7
6b 6a
UL Type 12 R4...R9
5
6
6
R7
R8
mm
in
mm
in
mm
245
9.65 262.5 10.33 345 13.58
27.61
718
2
R1..R3: × 4
R4: × 6
× 4
5
M6×12
Torx T25
2 N·m
(17 lbf·in)
R9
in
28.29