Burkert GENERIC 8400 Instructions de montage - Page 2
Parcourez en ligne ou téléchargez le pdf Instructions de montage pour {nom_de_la_catégorie} Burkert GENERIC 8400. Burkert GENERIC 8400 2 pages.
Once the Pt100 has been mounted onto the 8400 controller:
- plunge the Pt100 into a vessel filled with water: read out the temperature indicated by the
display of the controller.
- measure the real temperature of the water inside the vessel using a thermometer and note it
down.
Water
- Enter the Calibration mode of the controller.
- Select the T°-menu, validate and enter the difference between the real temperature and the
temperature measured by the 8400, i.e. 24.4 - 24.2 = 0.2 in the example above.
- Measure again the temperature of the water inside the vessel using the 8400 and check it
displays 24.4 °C
Bag with 20 Molex® connectors
Bag with 20 Molex® connectors mounted on cable
Subject to technical change without notice
© Bürkert 2001
Calibrate the controller
Readout = 24.2 ˚C
> 5s
+
ENTER
0......9
ENTER
000.2
T°
°C
*
0......9
* To enter a negative value, select the character at
END
the left hand side of the display and press
ENTER
until the minus sign appears.
Available accessory
Designation
2
Real temperature = 24.4 ˚C
ENTER
Order code
448849-Ind*1/Feb02
Generic 8400
0......9
448850
440258