Miller TM-268 Manuel technique - Page 13

Parcourez en ligne ou téléchargez le pdf Manuel technique pour {nom_de_la_catégorie} Miller TM-268. Miller TM-268 44 pages.

Miller TM-268 Manuel technique

7-2. Field Flashing

2
3
5
Tools Needed:
Belt Driven Generator
6
4
1
!
Stop generator.
Disconnect plug on wiring enclo-
sure cover. Loosen strain relief
bushing. Remove wiring enclosure
cover.
1
12 Volt Battery
2
Terminal 1T
3
Terminal 2T
4
Battery Negative (−) Lead
5
Battery Positive (+) Lead
6
Circuit Breaker CB1
Be sure CB1 is ON.
Flash the field by connecting negat-
ive of battery to 2T. With the genera-
tor running, momentarily connect
the battery positive to 1T.
Check for output voltage. If output
voltage is not present, repeat field
flashing procedure.
When output voltage is available,
stop generator and reinstall cover.
264 721−TPTM1
TM-268 819 Page 11