-How to move a parameter from the hidden menu to the first level and vice versa
Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing
SET+DPWN buttons. Is a parameter is part of the user level, when showed in the hidden menu the decimal
point will be lit.
How to lock the keyboard
Keep both UP and DOWN buttons pressed for more than 3 sec.
The poF, message will be displayed and the keyboard will be locked. At this point it will be possible only to
see the set point or the MAX o Min temperature stored
If a button is pressed more than 3 sec the PoF message will be displayed
How to unlock the keyboard
Keep pressed together for more than 3 sec the UP and DOWN keys til the Pon message will be
Displayed
The continuous cycle
When defrost is not in progress, it can be activated by holding the UP key pressed for about 3 sec. The
compressor operates to maintain the CCS set point for the time set through the CCt parameter. The cycle can
be terminated before the end of the set time using the same activation key UP for 3 sec.
The ON/OFF function
With "onF=oFF", pushing the ON/OFF key, the instrument is switched off. The "OFF" message is displayed.
In this configuration, the regulation is disabled. To switch the instrument n, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays are always supplied and under
voltage, even if the instrument is in standby mode.
Table of Parameters
DIXELL XR60CH c/ prog. XR 70 CH
DC-09.151-PRD
R02/22.04.2021