These instructions are intended for the installer of this pressure booster set. Please follow them 
carefully.  
 
The unit should only be installed by a competent person; A competent person is someone who is 
technically competent and familiar with safety practices and the hazards involved. 
 
Failure to install the equipment as recommended below could invalidate the warranty provided by 
AquaTech‐Pressmain to the purchaser. 
 
1.1 
ADDITIONAL WARNINGS 
 
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 & 0.4 
1.2 
ADDITIONAL CAUTIONS 
1.2.1 
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 & 0.4. 
1.2.2 
Ensure the Y strainer (100um) and isolation valve (supplied as loose item) is installed on the inlet to 
the breaktank (see fig 1.3), failure to install these will cause the solenoid to jamb and overflow the 
break tank. 
1.2.3 
Ensure the quick release filter (supplied as loose item) is installed in the breaktank overflow warning 
pipe (see fig 1.3) 
1.2.4 
Mains water pressure to unit should be between 1.0 and 3.0Bar. Ensure a pressure reducing valve set 
at a maximum of 3.0Bar is installed on the inlet to the breaktank if the mains water supply pressure 
exceeds 3.0Bar. 
1.2.5 
Ensure the pump is primed before starting otherwise the pump seal will be damaged and cause a leak 
(see fig 1.1a). 
1.2.6 
The maximum static outlet pressure is 12 metres for AB5‐45 (height from the pump discharge to the 
highest point of the system pipework), or 8 metres for AB5‐35. 
1.2.7 
Ensure the control vessel air charge is set correctly (1.3Bar) otherwise erratic operation will occur 
(pump will not start/stop correctly). 
1.2.8 
We recommend system pipework should be 22mm only reducing to 15mm at the terminal fitting. 
1.2.9 
Ensure the pressure vessel that is factory fitted to the pump assembly is still tight after transit, it 
should be hand tight only, DO NOT over tighten the pressure vessel, this will lead to damage to the 
vessel/fitting and subsequent leakage (see Fig 1.1b). 
 
Fig 1.1a Pump priming plug 
 
1.3 
PROCEDURE 
1.3.1 
OFF‐LOADING AT SITE 
AquaTech-Pressmain Instruction Manual\AquaBreak
1.  INSTALLATION INSTRUCTIONS  
 
 
 
 
 
Fig 1.1b Vessel hand tight only 
AquaBreak Series  
 
 
 