Filling/Emptying a tank or Low/High Level alarms
controlled by LW3 probe & timer: Using LSM & one
or two LW3 conductivity probes: -
1. fit probes to required length.
2. connect probes to required terminals
3. set DIL switches/timer as required, see section 2.2
e.g. for filling a tank between two levels (start probe "A" and stop
probe "B"): to energise relay 1 when start probe becomes dry and
release relay 1 when stop probe becomes wet, set all DIL
switches to OFF except switch 3 which is set to ON. Set timer to
0 seconds (Fully Anticlockwise).
Filling/emptying a tank or Low/High Level alarms
between one or two levels with a timer: Using LSM &
MSF-100 float switches: -
1. fix weight to cable at required length.
2. Wire float switches to required terminals
3. set DIL switches as required, see section 2.2
e.g. for emptying a tank between two levels (start probe "B" and
stop probe "A"): to energise relay 1 when start probe becomes
wet and release relay 1 when stop probe becomes dry, set all
DIL switches to OFF except switches 1 & 3 which are set to ON.
Set timer to 0 seconds (Fully Anticlockwise).
Filling/emptying a tank or Low/High level alarms
using Stainless Steel float switches: Using LSM &
one or two MSL-104 float switches: -
1. mount switches as required.
2. wire switches to required terminals
3. set DIL switches as required, see section 2.2
e.g. for high and low level alarm: to energise relay 1 when probe
"B" becomes wet (high level alarm) and relay 2 when probe "D"
becomes dry (low level alarm), set all DIL switches to OFF
except switches 2, 5 & 6 which are set to ON. To activate
audible alarm (where fitted) at high level, set switch 4 OFF,
alternatively to activate audible alarm (where fitted) at low level,
set switch 4 ON.