Error Code
LED Ring
Error Code
Error 01
Error 03
Error 05
Red light
flickering
Error 06
every 3
Error 07
seconds.
Error 08
Error 09
Error 10

5. Emergency Situations

AlphaESS cannot guarantee M48112-P absolute safety
Fire
In case of fires, make sure that the following equipment is available near the system.
★ SCBA (self-contained breathing apparatus) and protective gear in compliance with the Directive on
Personal Protective Equipment 89/686/EEC.
★ Novec 1230, FM-200, or dioxide extinguisher.
Note:
ABC extinguishers are not effective when the battery pack is on fire.
Batteries may explode when heated above 150°C. If possible, move the battery pack to a safe area
before it catches fire.
Leaking Batteries
If the battery pack leaks electrolyte, avoid contact with the leaking liquid or gas. If one is exposed to
the leaked substance, immediately perform the actions described below.
★ Inhalation: Evacuate the contaminated area, and seek medical attention.
★ Contact with eyes: Rinse eyes with flowering water for 5 minutes, and seek medical attention.
★ Contact with skin: Wash the affected area thoroughly with soap and water, and seek medical
attention.
★ Ingestion: Induce vomiting, and seek medical attention.
LED Display
Description
Hardware Error
Hardware Error
Hardware Error
Circuit Breaker Open
DIP Difference
LMU Disconnect(Slave)
SN Missing
LMU Disconnect(Master)
Wait for automated recovery.
In case problem is not resolved,
call in for repair.
Close circuit breaker after Shutting down
the battery system.
Keep consistence of DIP switches,
restart the system.
Reconnect the communication cable
Enter the serial number, restart the system
or call in for repair.
Reconnect the communication cable.
- 03 -