Alpha Group OutBack Power EnergyCell 200PLC Manuel du propriétaire - Page 6
Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} Alpha Group OutBack Power EnergyCell 200PLC. Alpha Group OutBack Power EnergyCell 200PLC 20 pages.
Installation and Operation
Materials Required
Tools (use insulated tools only)
o
Digital voltmeter
o
Socket wrench
o
Torque wrench calibrated in inch-pounds
o
Box end wrench
o
Battery lifting equipment (handles) and fork lift to lift pallets of batteries
o
Rubber gloves
o
Full face shield
o
Plastic apron
o
Portable eyewash
o
Spill kit
o
Fire extinguisher (class C)
Accessories
o
Interconnect bar (included)
o
Terminal cover (included)
o
Hardware (included)
o
Interconnect cables as needed
Storage and Environment Requirements
Temperatures
o
To achieve maximum life of EnergyCell batteries, it is recommended not to operate them in
average ambient temperatures outside the range of 68°F to 86°F (20°C to 30°C). High operating
temperatures will shorten a battery's life (see page 7).
o
Do not allow batteries to freeze, as this will damage them and could result in leakage.
o
Do not expose batteries to temperature variations of more than 5°F (3°C). This leads to voltage
imbalance between multiple batteries (or between battery cells if there is a temperature differential).
o
Batteries should be stored in a cool, dry location. The best storage temperature is 77°F (25°C), but
a range of –4°F to 104°F (–20°C to 40°C) is acceptable.
6
CAUTION: Fire Hazard
Install properly sized battery cabling and interconnect cables. The cable ampacity
must meet the needs of the system, including temperature, deratings, and any other
code concerns.
900-0227-01-00 Rev A