5b) Block Diagram

5c) Wiring Diagram RZ-
24 in an Ex-Proof
Hold-Open System
Without
Door Operator
Safe area
Central
unit
RZ-24
* Each ex-magnet has to be individually fused, with the fuse installed upstream of the magnet. You can find more in-
formation in the manual of the magnets. On site, the integration of a gas warning system must be checked by the ATEX
representative on the basis of explosion protection guidelines.
** Please refer to the Zener barrier manual for the detailed connection diagram.
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20220325
Electrical Connection and Installation of an Ex-Proof
Hold-Open System with RZ-24 - cont.
L1
N
Mains voltage
85 V AC....
265 V AC
(230 V AC)
ATTENTION: The bridge between the terminals 8 and 9,
which is put in factory, may not be removed!
The following wiring diagrams apply when the components of point 3a
are used. If for example other fire detectors (e.g. for installation outside
the hazardous area) are used, please contact us.
A hand release switch mounted outside the hazardous area, has to
be connected so that the Zener barrier is placed between it and the
hazardous area.
Fuse*
Zener barrier
Z779**
P
+
-
+24 -
Fire
Hold-open
alarm
system
loop
Hazardous area
zones 1 - 2
Up to 12 electromagnets
EM GD 50 EX or EM GD 70 EX
Max. 20 intrinsically safe
RM 3000IS EX smoke detectors or
Ex-proof
WM 3000IS EX heat detectors
hand
release
switch
700232
Screening, optional
(operational earth)
Technical Manual
RZ-24 Central
Fire alarm
potential-free
+24
-
8A/250V~/AC1
Jumper
Supply
placed
of other
in factory
consumers
Resistor 3.9 kΩ
Page 07.021.11
13
14
Ill. 4
placed in the
last detector
of the line
Ill. 5a