5. Protection
Protection
and recover
Parameter
Over voltage
Input Voltage
protection
Ui
and recover
Low voltage
Input Voltage
protection
Ui
and recover
Over tem.
protection
Tem.(T)
and recover
Overload
Output power S
Condition
IPower-12
IPower-22
Ui>16V
Ui>32V
Ui≤14.5V
Ui≤29V
Ui<10.8V
Ui<21.6V
Ui≥12.5V
Ui≥25V
Heat sink T>80℃
or Internal T>60℃
Heat sink T≤70℃
and Internal T≤50℃
S=1.2P
10
IPower-42
Output is OFF
Ui>64V
Green indicator fast flashing
Buzzer sounds
Green indicator on solid
Ui≤58V
The output is on
Output is OFF
Ui<43.2V
Green indicator slowly flashing
Buzzer sounds
Green indicator on solid
Ui≥50V
The output is on
Inverter turns OFF
Inverter turns ON
Output is OFF after 15min
e
Phenomenon