EPH Controls E 15402 Mode d'emploi - Page 2
Parcourez en ligne ou téléchargez le pdf Mode d'emploi pour {nom_de_la_catégorie} EPH Controls E 15402. EPH Controls E 15402 3 pages. Hardwired
![EPH Controls E 15402 Mode d'emploi](/uploads/products/server2/422216/422216.jpg)
CDT2-DS Room Thermostat
10. High and Low temperature limitation
An upper and lower temperature limit may be chosen.
Set
Press and hold the
and
"Limit OFF" will appear on the screen.
Press the
button to select "Limit ON" mode.
Set
Press the
button to con rm you wish to adjust the high limit temperature.
Press the
and
buttons to select the high limit temperature.
Press the
Set
button to select the low limit temperature mode.
Press the
and
buttons to select the low limit temperature.
Set
Press the
button and the thermostat is ready for operation.
"Limit" will appear on the screen.
To deactivate High and Low temperature limitation.
Set
Press and hold the
and
"Limit ON" will appear on the screen.
Press the
button to deactivate this function.
"Limit OFF" will appear on the screen.
Press the
Set
button and the thermostat is ready for operation.
11. Adjusting the switching di erential (Nor + DS)
Set
Press the
button once, Di set will appear on the screen.
The factory default switching di erential of 0.4 C will appear on the screen.
Press the
and
buttons to select the desired di erential from 0.2 - 1˚C.
Set
Press the
button to return to normal operation.
12. Adjusting the setpoint temperature
Press the
or
buttons to adjust the temperature setpoint.
13. Change the thermostat mode
a.) Nor - Normal On/O mode
b.) D.S. - Delay Start mode
c.) TPi - Time, Proportional, Integral mode
Slacken the fastening screw on the bottom of the thermostat with a
philips head screwdriver.
The thermostat is hinged and can be opened 180 degrees.
On the printed circuit board, you will see jumper, JP3 which has 4 pins.
The default position is the middle two pins which is Normal On/O mode.
Pull out the jumper and insert it in the top two pins for TPI control or insert
it in the bottom two pins for Delay Start control.
Close the thermostat and tighten the fastening screw.
Once the jumper has been changed the thermostat must be reset for
these changes to become e ective. (See section 8.)
buttons for 10 seconds.
buttons for 10 seconds.
EPH Controls Ireland
Sitecast Industrial Estate, Pouladu ,
Cork, T12 W665, Ireland
[email protected] www.ephcontrols.com
Hardwired
14. On/O control mode (Nor)
OFF
When the temperature falls below the setpoint temperature, the ame
symbol
When the temperature rises above the setpoint temperature, the ame
symbol
Temp
22˚C
21˚C
20˚C
19˚C
18˚C
17˚C
15. Delay start control mode (D.S.)
Delay start is an energy saving mode.
When the delay start function is active the ame symbol will continuously
ash on the screen. When in this mode the activation of the thermostat is
delayed by a variable time depending on the current temperature, setpoint
temperature and also the fall in temperature from when the delay start has
activated. See graph (15.1) Delay Start Control.
48.0
42.0
36.0
30.0
24.0
18.0
12.0
6.0
0.0
0
The ame symbol
When activated the thermostat will allow the heating system time to reach
the setpoint and delay start will remain inactive until it reaches this setpoint.
Delay start can be reactivated by:
Lowering the setpoint below the current temperature, pressing the set button
twice to set the temperature, then raising the setpoint above the zone
temperature.
The heating will be delayed as per the line on the graph.
If the di erence between the actual temperature and the setpoint is 1 C the
thermostat will delay starting for circa 40 minutes.
If the di erence between the actual temperature and the setpoint is 3 C the
thermostat will delay starting for circa 24 minutes.
If the di erence is 6 C or more, the heating will be switched on immediately.
The time delay will change if the temperature drops from the original
calculation.
To deactivate Delay Start, loosen the xing screw and change the position of
the jumper JP3. Change the position of the jumper to TPI or Nor.
EPH Controls UK
Unit E4, Welland Business Park, Valley Way, Market Harborough,
Leicestershire, LE16 7PS, United Kingdom
[email protected] www.ephcontrols.co.uk
Page 2 of 3
Operating Instructions
will appear and the thermostat will switch on.
will disappear and the thermostat will switch o .
Graph (14.1): On / O Control
0
20
40
60
80
Graph (15.1): Delay Start Control
1
2
3
4
5
Temperature below thermostat setting °C
will continue to ash until the thermostat activates.
Setpoint Temperature
Time Minutes
100
6