ABB UniSec Manuel d'utilisation et d'entretien - Page 11

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation et d'entretien pour {nom_de_la_catégorie} ABB UniSec. ABB UniSec 16 pages.

ABB UniSec Manuel d'utilisation et d'entretien
D I S T R I B U T I O N S O LU T I O N S
• Set the new sensor in the same position as the
old one.
• Fasten the strap around the busbar, then make
sure that the sensor remains firmly in contact
with the busbar and cannot move.
• Wrap the sensor strap around both busbars if
there are two busbars per phase.
c) Repeat the operation for all the sensors in the
panel.
Example of assembly on the cable connection
Example of assembly on cable connecting to CT
To make sure that communication is correct,
energize the circuit where the sensors are installed
using a current value of at least 50A AC and check
that the temperature measurement appears on the
APP or LHMI module.
d) Replacement of concentrator.
WARNING
Make sure that the low voltage
compartment is de-energized before
replacing the concentrator
11