Level Alarm
Cipax Part No.
606171, 10 m cable
606181, Wireless with batteries.
Attach the level sensor (1) with supplied M8
screw, washer and nut at the edge of the tank as shown in
the picture. First drill an 8 mm hole approximately 90
degrees away from the Inlet pipe.
The alarm will be triggered when there are aprox 150 l
remaining until the tank is full. If desired the hose clamp
can be moved from the set position to trigger the alarm
sooner or later.
For Part No. 606181: Position the wireless sender (2) as high
as possible and attach with the supplied screw.
For Part No. 606171 drill a 16 mm hole and deburr the hole! Attach the cable gland.
Make a small hole with an owl or similar and pull the cable through.
______________________________________________________________
Management
The tank, equipment and accessories must be handled with care. Do not allow these parts to
come into contact with objects that may cause damage. On receiving delivery and prior to
installation, inspect the products carefully for any signs of damage.
Lifting the tank
The tank is to be lifted using soft bands that
can be threaded through the holes.
The tank must be empty when lifted.