"Spot" is a safety light beam which is available in two versions, Spot 10 for distances up to 10 m
and Spot 35 for distances up to 35 m. The light beams can be mounted at different heights and be
angled around a machine using special mirrors and brackets. For indication there are LED´s on the
transmitter and on the receiver which indicate "contact" between transmitter and receiver and
safety status. The "contact" information is available via the light beam receiver connection cables.
Spot 35
Spot 10
Safety inputs Vital 2
Vital 2 has two single channel inputs for connection to dynamic sensors such as Jokab "Eden"
sensors and "Tina" components. Each input function has two input terminals, one for an odd
number of sensors and one for an even number of sensors.
Safety inputs Vital 3
Input function 1 is a dual channel input for closing switches where one channel is a dynamic signal,
and the other a static +24V signal. Input function 2 is a single channel input of the same type as in
Vital 2.
Output groups
There are two groups of outputs:
Output group 1: Q1 and Q2.
Output group 2: Q11, Q12 and Q13. (Q13 is non-safe)
Reset / Auto reset
There are two separate reset functions, Reset 1 and Reset 2. Depending on mode selection they
work a bit differently (see Mode selection). They can be set to manual or automatic reset
independently of each other with the inputs Auto reset 1 and Auto reset 2.
Manual reset
For manual reset a pushbutton shall be connected to X1 (Reset 1) or X11 (Reset 2). Monitoring
contacts of external devices shall be placed in series with the pushbutton. When manual reset is
selected X4 (for Reset 1) and X14 (for Reset 2) works as reset indicator outputs to which a lamp
can be connected.
Auto reset
For auto reset, input X4 (Auto reset 1) or X14 (Auto reset 2) shall be connected to +24V.
Monitoring contacts of external devices shall be placed between +24V and X1(for Auto reset 1) or
X11 (for Auto reset 2). If monitoring contacts are not used X1 and X11 shall be connected to +24V.