Importance Considerations
Electrical Service
110V, 60Hz, 15Amp GFCI protected grounded circuit MUST be used to supply power each individual pedicure
spa. And the main circuit breaker MUST be at 25Amp. For maximum of two units per each electrical outlet.
Water pressure
-
To fill the basin correctly up to level, normal water pressure of 30 to 80 P.S.I is required.
-
Maximum Pressure: 150 psi (10 bars)
-
Minimum Pressure: 10 psi (69kPa)
Water temperature
-
The hot water supply temperature must not exceed 140F. Adjust your hot water accordingly. For hot and cold
water supply fittings and drain fittings location, see below diagram. Carefully connect the water supply line to
the appropriate fittings located on the rear of the pedicure spa.
-
Working Temperature: 33F to 140F constant; intermittent to 180f (0.6C to 60C sustained; intermittent to 82.2C)
-
Recommended Flow: 1.5 gpm
** Backflow Preventor/Vacuum Breaker**
Due to differences in construction layout of salons and city plumbing codes, please contact your local plumber
to fulfill your needs as required. Backflow preventers are not supplied by the pedicure spa manufacturer. The
Plumber MUST provide Backflow Preventor according to building code requirement.
Drain Facilities
The pedicure spa Drain must meet local plumbing codes. Check valve for Drain (not Provided) Must be installed
by a licensed plumber.
UL LISTED / CE CERTIFIED
Compliance with following Code (s): Uniform Plumbing Code, National Plumbing Code of Canada and
international Plumbing Code. Also, Compliance with following Standard (s): ASME A112.18.3M / A112.18.1M,
CSA B125, NSF / ANSI 61
ANSI - American National Institute, ASME - American Society of Mechanical Engineers, CSA - Canadian Standard
Association IAPMO - International Association of Plumbing and Mechanical Officials, UL - Underwriters
Laboratory
All AYC pedicure spa chair has been compliance with requirements for Whirlpool bath appliances contained in
ASME / ANSI A122.19.7M-1995, CSA C22.2 No. 68-69
Installation Summary
The installation must comply with local, state, and federal building, plumbing and electrical codes, where
applicable. A licensed plumber should complete the plumbing of the pedicure spa.
Note: Failure to comply with federal, state, or local codes and ordinances will result in warranty being nullified