3 NETWORK CONNECTION AND CONFIGURATION

Warnings. When connecting a PROFIBUS-enabled AX400 Series analyzer to a PROFIBUS-DP network:
• Use shielded data lines and ensure they are not reversed.
• Ensure all data lines are routed clear of the source of any strong electrical and magnetic fields.
• Refer to the relevant User Guide for all other installation and connection details.
3.1 Network Connections – Fig. 3.1
Terminal Block C
(Profibus-DP Enabled Option Board)
A – Wall- /Pipe-Mount AX400 Series Analyzers
PROFIBUS-DP Data Cable
Data Signal
Cable Color
A
Green
B
Red
Braided
N/A
Screen
4
Description
Negative data line. Connect to pin 8 on Profibus-DP equipment
with 9-way D-type connectors
Positive data line. Connect to pin 3 on Profibus-DP equipment
with 9-way D-type connectors
Cable screen. Usually connected to the D-type shell or pin 1 on
Profibus-DP equipment with 9-way D-type connectors
Warning. Before making any electrical connections,
refer to the
in Section 6 of the relevant User Guide.
Warnings
Fig. 3.1 Network Cable Connection
Terminal Block C
(Profibus-DP Enabled Option Board)
C1
Not used
C2
Not used
C3
PROFIBUS-DP Data Cable B – Red
C4
PROFIBUS-DP Data Cable A – Green
C5
PROFIBUS-DP Data Cable – Braided Screen
C6
Not Used
C7
C8
C9
C10
C11
See User Guide
C12
C13
C14
C15
C16
B – Panel-Mount AX400 Series Analyzers