Siemens SIMATIC ET 200S Manuel - Page 21

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Siemens SIMATIC ET 200S. Siemens SIMATIC ET 200S 24 pages. Distributed i/o digital electronic module 4do dc24v/2a hf
Également pour Siemens SIMATIC ET 200S : Manuel de l'opérateur (18 pages), Manuel (16 pages), Manuel de l'utilisateur (16 pages), Manuel de l'utilisateur (26 pages), Manuel (37 pages), Manuel (24 pages), Manuel des fonctions (40 pages), Mode d'emploi (4 pages), Mode d'emploi original (19 pages), Mode d'emploi original (20 pages), Manuel (34 pages), Manuel (14 pages), Mode d'emploi original (17 pages), Mode d'emploi original (19 pages), Manuel (16 pages), Manuel (28 pages), Manuel (12 pages), Manuel (32 pages), Manuel (18 pages), Manuel (12 pages), Manuel (28 pages), Manuel (22 pages), Manuel (22 pages), Manuel (36 pages), Manuel (16 pages)

Siemens SIMATIC ET 200S Manuel
Non-isolated measuring encoders
The non-isolated measuring encoders are connected to the local ground potential. You must
connect M
potential differences U
measuring points.
If the permitted value for U
between the measuring points.
The following schematic representation illustrates the connection of non-isolated measuring
encoders to an optically isolated analog input module.
Connection of non-isolated measuring encoders to an optically isolated analog input module:
5
4
Operating four-wire transmitters on an external voltage supply
If there is electrical isolation between the output and the transmitter supply, you can connect
the transmitter to the 2 AI I 4WIRE ST without the need for additional connections.
If there is no electrical isolation between the output and the transmitter supply, you can only
connect the transmitter to the 2 AI I 4WIRE ST if the reference potential of the supply
voltages (24 V DC) is the same.
If there is an increase in interference radiation, it is recommended that you connect M- to
M
ANA
2AI I 4WIRE ST analog electronic module (6ES7134-4GB11-0AB0)
Manual, 04/2007, A5E01076100-01
to the ground potential. Depending on local conditions or interference,
ANA
(static or dynamic) can occur between the locally distributed
CM
CM
Logic
Backplane bus
Ground bus
Equipotential bonding conductor
Non-isolated measuring encoders
on the terminal module of the 2 AI I 4WIRE ST.
is exceeded, there must be equipotential bonding conductors
3
5.1 Connecting measuring sensors
1
2
Connecting
21