Également pour Siemens SIMATIC ET 200SP : Manuel (40 pages), Manuel de l'utilisateur (21 pages), Manuel (34 pages), Manuel (48 pages), Manuel (30 pages), Manuel (34 pages), Manuel (37 pages), Manuel (36 pages), Manuel (44 pages), Manuel (31 pages), Manuel (35 pages), Manuel (23 pages), Manuel de configuration (20 pages), Manuel (34 pages), Manuel (29 pages), Manuel (33 pages), Manuel (31 pages), Manuel de l'utilisateur (32 pages), Manuel (31 pages), Manuel (28 pages), Manuel (41 pages), Manuel (32 pages), Manuel (49 pages), Manuel (24 pages), Manuel (34 pages), Manuel (41 pages), Manuel (30 pages), Manuel (31 pages), Manuel (27 pages), Manuel (24 pages), Manuel (24 pages), Manuel (25 pages), Manuel (49 pages), Manuel (40 pages), Manuel (38 pages), Manuel (39 pages), Informations sur le produit (24 pages), Manuel (32 pages), Informations sur le produit (10 pages), Manuel de l'équipement (43 pages), Manuel (33 pages), Manuel de l'équipement (44 pages), Mode d'emploi original (6 pages), Manuel (35 pages), Manuel (28 pages), Manuel de l'équipement (32 pages), Manuel (50 pages), Manuel (30 pages), Manuel (26 pages), Manuel (28 pages), Manuel (34 pages), Manuel (44 pages), Manuel (33 pages), Manuel de l'équipement (42 pages), Manuel d'instructions original (16 pages)

Siemens SIMATIC ET 200SP Informations sur le produit
Fail-safe modules
ET 200SP modules with integrated safety functions that can be used for safety-related
operation (safety mode).
Fail-safe systems
Fail-safe systems (F-systems) remain in a safe state or immediately assume another safe
state as soon as particular failures occur.
Fault response time
The maximum fault response time of an F-system defines the interval between the
occurrence of any fault and a safe reaction at all affected fail-safe outputs.
For → F-systems overall: The maximum fault response time defines the interval between the
occurrence of any fault at any → F-I/O and the safe reaction at the corresponding fail-safe
output.
For digital inputs: The maximum fault response time defines the interval between the
occurrence of the fault and the safe reaction at the backplane bus.
For digital outputs: The maximum fault response time defines the interval between the
occurrence of the fault and the safe reaction at the digital output.
Fault tolerance time
The fault tolerance time of a process is the time a process can be left unattended without risk
to life and limb of the operating personnel, or damage to the environment.
Any type of F-system control is tolerated within this fault tolerance time, i.e. the → F-system
can control its processes incorrectly or even not at all. The fault tolerance time depends on
the type of process and must be determined on a case-by-case basis.
F-CPU
An F-CPU is a central processing unit with fail-safe capability that is permitted for use in
SIMATIC Safety. A standard user program can also be run on the F-CPU.
F-I/O
Collective name for fail-safe inputs and outputs available in SIMATIC S7 for integration into
the SIMATIC Safety F-system. Available F-I/O modules:
● Fail-safe I/O module for ET 200eco
● Fail-safe signal modules S7-300 (F-SMs)
● Fail-safe modules for ET 200S
● Fail-safe modules for ET 200SP
● Fail-safe DP standard slaves
● Fail-safe PA field devices
● Fail-safe IO devices
ET 200SP distributed I/O system
Product Information, 07/2013, A5E32288220-AA
Glossary
33