Également pour Siemens SIMATIC ET 200SP : Manuel (40 pages), Manuel de l'utilisateur (21 pages), Manuel (34 pages), Manuel (48 pages), Manuel (30 pages), Manuel (34 pages), Manuel (37 pages), Manuel (36 pages), Manuel (44 pages), Manuel (31 pages), Manuel (35 pages), Manuel (23 pages), Manuel de configuration (20 pages), Manuel (34 pages), Manuel (29 pages), Manuel (33 pages), Manuel (31 pages), Manuel de l'utilisateur (32 pages), Manuel (31 pages), Manuel (28 pages), Manuel (41 pages), Manuel (32 pages), Manuel (49 pages), Manuel (24 pages), Manuel (34 pages), Manuel (41 pages), Manuel (30 pages), Manuel (31 pages), Manuel (27 pages), Manuel (24 pages), Manuel (24 pages), Manuel (25 pages), Manuel (49 pages), Manuel (40 pages), Manuel (38 pages), Manuel (39 pages), Informations sur le produit (24 pages), Manuel (32 pages), Informations sur le produit (10 pages), Manuel de l'équipement (43 pages), Manuel (33 pages), Manuel de l'équipement (44 pages), Mode d'emploi original (6 pages), Manuel (35 pages), Manuel (28 pages), Manuel de l'équipement (32 pages), Manuel (50 pages), Manuel (30 pages), Manuel (26 pages), Manuel (28 pages), Manuel (34 pages), Manuel (44 pages), Manuel (33 pages), Manuel de l'équipement (42 pages), Manuel d'instructions original (16 pages)

Siemens SIMATIC ET 200SP Informations sur le produit

Product overview

1.1

What are fail-safe automation systems and fail-safe modules?

Fail-safe automation systems
Fail-safe automation systems (F-systems) are used in systems with higher-level safety
requirements. F-systems serve to control processes and ensure that they are in a safe state
immediately after shutdown. In other words, F-systems control processes in which an
immediate shutdown does not endanger persons or the environment.
Fail-safe modules
The key difference between fail-safe modules (F-modules) and standard ET 200SP modules
is that they have an internal two-channel design. The two integrated processors monitor
each other, automatically test the input and output circuits, and switch the F-I/O module to a
safe state in the event of a fault.
The F-CPU communicates with the fail-safe modules via the fail-safe PROFIsafe bus profile.
Fail-safe power modules, together with the respective BaseUnit, serve the load voltage
supply of the potential group and the safety-oriented tripping of the load voltage for standard
output modules.
Fail-safe digital input modules detect the signal states of safety-oriented sensors and send
the relevant safety message frames to the F-CPU.
Fail-safe digital output modules are suitable for safety-related shutdown procedures with
short circuit and cross-circuit protection up to the actuator.
Possible uses of ET 200SP with fail-safe modules
The use of ET 200SP with fail-safe modules allows conventional configurations in safety
engineering to be replaced with PROFNET IO components. This includes the replacement of
switching devices for emergency STOP, protective door monitors, two-hand operation, etc.
ET 200SP fail-safe modules are supported with the STEP 7 Safety Advanced optional
package V12 including HSP 54 or higher.
ET 200SP fail-safe modules are supported with IM155-6PN ST as of firmware V1.1.
ET 200SP distributed I/O system