Siemens SIMATIC ET 200SP Manuel - Page 17

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 23 pages. Distributed i/o system
Également pour Siemens SIMATIC ET 200SP : Manuel (40 pages), Manuel de l'utilisateur (21 pages), Manuel (34 pages), Manuel (48 pages), Manuel (30 pages), Manuel (34 pages), Informations sur le produit (38 pages), Manuel (37 pages), Manuel (36 pages), Manuel (44 pages), Manuel (31 pages), Manuel (35 pages), Manuel de configuration (20 pages), Manuel (34 pages), Manuel (29 pages), Manuel (33 pages), Manuel (31 pages), Manuel de l'utilisateur (32 pages), Manuel (31 pages), Manuel (28 pages), Manuel (41 pages), Manuel (32 pages), Manuel (49 pages), Manuel (24 pages), Manuel (34 pages), Manuel (41 pages), Manuel (30 pages), Manuel (31 pages), Manuel (27 pages), Manuel (24 pages), Manuel (24 pages), Manuel (25 pages), Manuel (49 pages), Manuel (40 pages), Manuel (38 pages), Manuel (39 pages), Informations sur le produit (24 pages), Manuel (32 pages), Informations sur le produit (10 pages), Manuel de l'équipement (43 pages), Manuel (33 pages), Manuel de l'équipement (44 pages), Mode d'emploi original (6 pages), Manuel (35 pages), Manuel (28 pages), Manuel de l'équipement (32 pages), Manuel (50 pages), Manuel (30 pages), Manuel (26 pages), Manuel (28 pages), Manuel (34 pages), Manuel (44 pages), Manuel (33 pages), Manuel de l'équipement (42 pages), Manuel d'instructions original (16 pages)

Siemens SIMATIC ET 200SP Manuel
5.2

Load voltage status

Load voltage status
The firmware of the module cannot detect the status of the load voltage.
If the "Load voltage status" function tied to the server module is used, a "1" is always
displayed in the status bit for a slot with the DQ 4×24..230VAC/2A ST. Even when the load
voltage is not applied.
The state of the load voltage at the terminal does not impact the PROFIenegy behavior.
5.3

Interrupts

The DQ 4x24...230VAC/2A ST digital output module supports diagnostics interrupts.
Diagnostics interrupts
The module generates a diagnostic interrupt at the following events:
● Channel temporarily unavailable
● Parameter assignment error
5.4

Diagnostics alarms

Diagnostics alarms
A diagnostics alarm is output for each diagnostics event and the DIAG LED flashes on the
module. The diagnostics alarms can, for example, be read from the diagnostics buffer of the
CPU. You can evaluate the error codes with the user program.
Table 5- 4
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarm
Parameter assignment
error
Channel/component
temporarily unavailable
DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1)
Manual, 03/2015, A5E32043575-AB
Error code
10
The module cannot evaluate parameters
H
for the channel.
Incorrect parameter assignment.
1F
Firmware update is currently in progress or
H
has been canceled. The module does not
read in process values in this state.
Meaning
Interrupts/diagnostics alarms
5.2 Load voltage status
Solution
Correct the parameter assignment
Wait for firmware update
Restart the firmware update
17