Siemens SIMATIC ET 200SP Manuel - Page 41

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Siemens SIMATIC ET 200SP. Siemens SIMATIC ET 200SP 41 pages. Distributed i/o system
Également pour Siemens SIMATIC ET 200SP : Manuel (40 pages), Manuel de l'utilisateur (21 pages), Manuel (34 pages), Manuel (48 pages), Manuel (30 pages), Manuel (34 pages), Informations sur le produit (38 pages), Manuel (37 pages), Manuel (36 pages), Manuel (44 pages), Manuel (31 pages), Manuel (35 pages), Manuel (23 pages), Manuel de configuration (20 pages), Manuel (34 pages), Manuel (29 pages), Manuel (33 pages), Manuel (31 pages), Manuel de l'utilisateur (32 pages), Manuel (31 pages), Manuel (28 pages), Manuel (32 pages), Manuel (49 pages), Manuel (24 pages), Manuel (34 pages), Manuel (41 pages), Manuel (30 pages), Manuel (31 pages), Manuel (27 pages), Manuel (24 pages), Manuel (24 pages), Manuel (25 pages), Manuel (49 pages), Manuel (40 pages), Manuel (38 pages), Manuel (39 pages), Informations sur le produit (24 pages), Manuel (32 pages), Informations sur le produit (10 pages), Manuel de l'équipement (43 pages), Manuel (33 pages), Manuel de l'équipement (44 pages), Mode d'emploi original (6 pages), Manuel (35 pages), Manuel (28 pages), Manuel de l'équipement (32 pages), Manuel (50 pages), Manuel (30 pages), Manuel (26 pages), Manuel (28 pages), Manuel (34 pages), Manuel (44 pages), Manuel (33 pages), Manuel de l'équipement (42 pages), Manuel d'instructions original (16 pages)

Siemens SIMATIC ET 200SP Manuel
Representation of analog values
B.3 Representation of analog values in the current measuring ranges
B.3

Representation of analog values in the current measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table B- 6
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
* For measuring type "2-wire transducer", negative values are not possible for the range "0 to 20 mA".
Therefore, no underrange or underflow exists here.
40
Current measuring ranges 0 to 20 mA and 4 to 20 mA
Current measuring range
Hex.
0 to 20 mA *
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
ED00
-3.52 mA
8000
<-3.52 mA
4 to 20 mA
>22.81 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
<1.185 mA
Analog Input Module AI 4xU/I 2-wire ST (6ES7134-6HD01-0BA1)
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Manual, 12/2017, A5E03572832-AD