Également pour Siemens SIMATIC ET 200SP : Manuel (40 pages), Manuel de l'utilisateur (21 pages), Manuel (34 pages), Manuel (48 pages), Manuel (30 pages), Manuel (34 pages), Informations sur le produit (38 pages), Manuel (37 pages), Manuel (36 pages), Manuel (44 pages), Manuel (31 pages), Manuel (35 pages), Manuel (23 pages), Manuel de configuration (20 pages), Manuel (34 pages), Manuel (29 pages), Manuel (33 pages), Manuel (31 pages), Manuel de l'utilisateur (32 pages), Manuel (31 pages), Manuel (28 pages), Manuel (41 pages), Manuel (32 pages), Manuel (49 pages), Manuel (24 pages), Manuel (34 pages), Manuel (41 pages), Manuel (30 pages), Manuel (31 pages), Manuel (27 pages), Manuel (24 pages), Manuel (24 pages), Manuel (25 pages), Manuel (49 pages), Manuel (38 pages), Manuel (39 pages), Informations sur le produit (24 pages), Manuel (32 pages), Informations sur le produit (10 pages), Manuel de l'équipement (43 pages), Manuel (33 pages), Manuel de l'équipement (44 pages), Mode d'emploi original (6 pages), Manuel (35 pages), Manuel (28 pages), Manuel de l'équipement (32 pages), Manuel (50 pages), Manuel (30 pages), Manuel (26 pages), Manuel (28 pages), Manuel (34 pages), Manuel (44 pages), Manuel (33 pages), Manuel de l'équipement (42 pages), Manuel d'instructions original (16 pages)

Siemens SIMATIC ET 200SP Manuel
Parameters/address space
4.3 Address space
Port configuration
With a IO-Link Master CM 4xIO-Link as of firmware version V2.2, you can commission the
IO-Link port of the IO-Link master and the connected IO-Link devices in two different ways:
● Port configuration without S7-PCT
● Port configuration with S7-PCT
Port configuration without S7-PCT
Requirements
You have activated the "Port configuration without S7-PCT" check box in the configuration of
the IO-Link master in STEP 7.
Procedure
You configure the IO-Link master directly in STEP 7:
● Activate the diagnostics
● Configuration of the I/O data lengths for each port
● Activate the PortQualifierInformation (PQI)
● Port mode:
– Operation in "IO-Link Autostart" mode (default)
– Operation in "IO-Link Manual" mode
– Operated as DI
– Operated as DQ
– Deactivated
Port configuration with S7-PCT
Requirements
You have deactivated the "Port configuration without S7-PCT" check box in the configuration
of the IO-Link master in STEP 7.
Procedure
You configure the IO-Link master with the Port Configuration Tool S7-PCT, V3.2 or higher.