Également pour Siemens SIMATIC ET 200SP : Manuel (40 pages), Manuel de l'utilisateur (21 pages), Manuel (34 pages), Manuel (48 pages), Manuel (30 pages), Manuel (34 pages), Informations sur le produit (38 pages), Manuel (37 pages), Manuel (36 pages), Manuel (44 pages), Manuel (31 pages), Manuel (35 pages), Manuel (23 pages), Manuel de configuration (20 pages), Manuel (34 pages), Manuel (29 pages), Manuel (33 pages), Manuel (31 pages), Manuel de l'utilisateur (32 pages), Manuel (31 pages), Manuel (28 pages), Manuel (41 pages), Manuel (32 pages), Manuel (49 pages), Manuel (24 pages), Manuel (34 pages), Manuel (41 pages), Manuel (30 pages), Manuel (31 pages), Manuel (27 pages), Manuel (24 pages), Manuel (24 pages), Manuel (25 pages), Manuel (49 pages), Manuel (40 pages), Manuel (38 pages), Manuel (39 pages), Informations sur le produit (24 pages), Manuel (32 pages), Informations sur le produit (10 pages), Manuel de l'équipement (43 pages), Manuel (33 pages), Manuel de l'équipement (44 pages), Mode d'emploi original (6 pages), Manuel (28 pages), Manuel de l'équipement (32 pages), Manuel (50 pages), Manuel (30 pages), Manuel (26 pages), Manuel (28 pages), Manuel (34 pages), Manuel (44 pages), Manuel (33 pages), Manuel de l'équipement (42 pages), Manuel d'instructions original (16 pages)

Siemens SIMATIC ET 200SP Manuel
2 Solution
Sequence of the core functionality
Figure 2-3
1
Switching on
2
IOL Reader
Finished
Watchdog timer
3
Transponder
detected
4
Finished
Switching off
5
IOL Reader
Table 2-4
No.
1.
Job triggered by the user.
2.
Switch on IOL reader by selecting the
"LIOLink_RF299_SwitchAntenna"
block.
3.
Start the watchdog timer.
4.
Read the transponder with the
"LIOLink_RF200_ReadTag" block.
5.
Switch off IOL reader by selecting the
"LIOLink_RF200_SwitchAntenna"
block.
Read/write data with IO-Link
Entry ID: 73565887,
V3.4,
Wait for
trigger
Start
Error
No transponder
detected
5 s
Read/write
function
Error
Action
06/2022
Error and
status output
Note
With watch table, user program or HMI.
The watchdog timer monitors whether a
transponder is located within the detection
area within a monitoring time of 5 seconds.
Executed if the read job has been
executed successfully or an error has
occurred during the read job.
Switching off the antenna field terminates
the read function.
11