Également pour Siemens SIMATIC ET 200SP HA : Manuel (50 pages), Manuel (34 pages), Manuel (38 pages), Manuel de l'équipement (44 pages), Manuel de l'équipement (50 pages), Manuel de l'équipement (38 pages), Manuel de l'équipement (46 pages), Manuel de l'équipement (42 pages), Manuel de l'équipement (44 pages), Manuel de l'équipement (36 pages), Manuel de l'équipement (38 pages)

Siemens SIMATIC ET 200SP HA Manuel
Displays and interrupts
6.1 Status and error displays
RN LED
Table 6-1
Status and error displays of the RN LED
RN LED
No supply voltage or insufficient supply voltage at the
interface module.
Off
Interface module is deactivated.
Flashes
Interface module is not configured.
ET 200SP HA starts up.
ET 200SP HA parameters are assigned
ET 200SP HA is exchanging data with the IO Control‐
ler.
On
ER LED
Table 6-2
Error displays of the ER LED
ER LED
Group fault and group fault for channels
Flashes
Configured settings do not match the actual configu‐
ration of the ET 200SP HA.
Impermissible configuration states
Parameter assignment error in the I/O module
Note
Configuration errors are only checked when the station starts up and not during a CiR or H-
CiR process.
20
Meaning
Meaning
Remedy
Check the supply voltage or switch it on at the inter‐
face module.
Check the backplane bus for short-circuit
Activate the interface module with the configuration
software or the user program.
Configure the interface module with the configuration
software.
---
---
Remedy
Evaluate the diagnostics and eliminate the error.
Check the configuration of the ET 200SP HA for miss‐
ing modules, defective modules or the presence of
non-configured modules.
You can find information about the hardware configu‐
ration of the ET 200SP HA in the system manual
ET 200SP HA Distributed I/O System ; System Plan‐
ning, Hardware Configuration.
Evaluate the display of the module information in HW-
Konfig and eliminate the error in the corresponding I/
O module.
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA