Siemens SIMATIC ET 200SP HA Manuel - Page 8

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Siemens SIMATIC ET 200SP HA. Siemens SIMATIC ET 200SP HA 32 pages. Distributed i/o devices busadapter for distributed i/o
Également pour Siemens SIMATIC ET 200SP HA : Manuel (50 pages), Manuel (34 pages), Manuel (38 pages), Manuel de l'équipement (44 pages), Manuel de l'équipement (50 pages), Manuel de l'équipement (38 pages), Manuel de l'équipement (46 pages), Manuel de l'équipement (42 pages), Manuel de l'équipement (44 pages), Manuel de l'équipement (36 pages), Manuel de l'équipement (38 pages)

Siemens SIMATIC ET 200SP HA Manuel
Product overview
2.1 Properties
The interface has the following technical properties:
● Supply voltage 1L+ 24 V DC (SELV/PELV).
The supply voltage is fed via the carrier module.
The connection plug is included in the scope of delivery of the interface module.
● PROFINET IO connection via BusAdapter (see following paragraph, "Accessories")
The interface supports the following functions:
● Firmware update
● I&M identification data
● Pulling and plugging modules in RUN
● Value status QI
● IO redundancy
● Time stamping
● Multi Hot Swap (pulling/plugging of multiple I/O modules during operation)
● Saving service data
● Recording the value status of I/O modules
● Reference temperature distribution
You can configure the interface with HW Config and integrate it into your system
Note
The IM 155‑6 PN HA cannot be pulled/plugged when the associated connector for the supply
voltage is plugged in.
PROFINET IO functions
The interface supports the following PROFINET IO functions:
● Integrated BusAdapter with 2 ports
● Supported Ethernet services: ping, arp, network diagnostics (SNMP)/MIB-2, LLDP-MIB and
MRP-MIB
● Port diagnostics
● Disabling of ports
● Minimum update time of 250 µs
● Device replacement without programming device (PG)
● Reset to factory settings via PROFINET IO
● System redundancy S2
● System redundancy R1
● Media redundancy (MRP)
● Support of submodules on suitable I/O modules
8
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA